Magnum 8000X Mixed-Media Fiber Hubs

Installation and User Guide (05/ 02)

The hub models with the internal -48VDC, 24VDC &125VDC Dual-Source power supply are designed for installations where a battery plant is the power source, and where two separate power sources are utilized in order to increase operational uptime and to simplify maintenance.

The functionality of the Magnum 8000X-48VDC, 24VDC or 125VDC Dual- Source Option hubs are identical to the standard AC-powered models. All Port Module, SNMP and stacking options are available for configuration with Dual-Source Option units. Refer to the main sections of this Installation and User Guide for a detailed description of the Magnum 8000X Hubs.

C3.0 DUAL-SOURCE OPTION, THEORY OF OPERATION

The Dual-Source DC power option is designed using diodes inside of the hub

on each DC power input line. A diode is placed in each of the four input lines (behind the four external power connection terminals) so that power from an external source can only flow into the hub. This allows the hub to operate whenever DC power is correctly applied to either or both

of the two inputs.

A+

HUB

A-

SUPPLY

+

B-

- FUSE

 

B+

 

GND

CHASSIS

GND

 

C4.0 FEATURES AND BENEFITS OF THE DUAL-SOURCE DESIGN

a)The hub can receive power from either input, “A” or “B”. The hub will normally draw its power from the DC source with the highest voltage at a given time.

b)The hub will not allow power to flow from a higher voltage input to a lower voltage input, i.e. the two DC power sources are not mixed together by the hub.

c)When one correct DC input is present, the hub will receive power if the other DC input is absent, or even if it is connected with reverse polarity or shorted or grounded.

d)Reverse polarity connections, if they should accidentally occur on either input, will not damage the hub or power supply internally (nor will it blow the fuse in the internal power supply) because of the blocking action of the diodes. This is true even if one input connection is reversed while the hub is operating from the other source.

e)The hub will not receive power (and will not work) when both inputs are simultaneously absent or are both incorrectly connected.

C5.0 INSTALLATION

This section describes the proper connection of the -48VDC, 24VDC & 125VDC dual source leads to the -48VDC, 24VDC & 125VDC power terminal block on the Magnum 8000X hub (shown in Figure C4.0).

The -48VDC terminal block on the Magnum 8000X is located on the right rear of the unit and is equipped with five (5) screw-down lead posts (see Figure C5.0). The primary terminals are identified as positive (A+), negative (A-), and the secondary power terminals as negative (B-), positive (B+). The chassis “earth” or ground (GND), is a threaded post with a #6 nut. The dual source terminal block for 24VDC and 125VDC are similar.

www . GarrettCom . com

54

Image 61
Contents Mixed-Media Fiber Hubs Trademarks Magnum Mixed-Media Fiber Hubs Installation and User GuideContacting GarrettCom, Inc GarrettCom, IncPersonal Hubs, 10Mb series Personal Switches , 10/100MbMedia Converters, 10Mb and 100Mb series Introduction Magnum 8000X MIXED-MEDIA Fiber HUB Roubleshooting Revisions Power Supply, AC Internal Technical SpecificationsNetwork Standards Maximum Ethernet Segment or Domain LengthsManual Switches DC Power Supply OptionsLED Indicators WarrantyPM Model # Ieee Standard Speed Connector type Specifications Switching Port Modules SPMs for bonus portMagnum 8000X Mixed-Media Fiber Hubs Switch Port Modules SPMs for the Bonus Port8000X Front Port Modules PMs Magnum 8000X Mixed-Media Fiber Hubs Product Description General InformationA Magnum 8000X, Front View Magnum 8000X Fiber Hub ChassisPort Modules PMs C Magnum 8000X Rear Panel ViewFPM-MSC, FPM-MST, FPM-MV45, FPM-SXMST, & PM-FP Switch Port Modules SPMsFiltering and Forwarding / Address Learning 5a Inside view of Magnum 8000X with SPM installed. Rear viewSeg Not in table Add source to table Forward Filter None Magnum SPM-FDST Magnum SPM-FDSSC Magnum SPM-FDSCMagnum SPM-TTX SPM Specification Summary TableStacking Magnum Mixed-Media 8000X Fiber Hubs 10 /100 Speed Auto-sensing 8000X front copper ports only7a a stack of one Magnum 8000X and two DS-8016-A’s Internal view of 8000X with bridge module installed LEDs for Chassis and PM Cards Stackable and Scaleable ConfigurationsApplications Magnum 8000X has 16 ports per unit Connecting Ethernet Media Magnum 8000X InstallationLocating the Magnum Connecting Fiber Optic SC-type, Snap-In Connecting Fiber Optic ST-type, twist-lockCopper Media Ieee Standard Connecting Single-Mode Fiber OpticBit Time per Meter BT/m Magnum 8000X Mixed-Media Fiber Hubs 1b Multiple cascaded Magnum 8000X Mixed-Media hubs PDV = X + 100 + 80 + 80 +Length m Max. User Max. Inter HubsConnections to NICs which support Auto-Negotiation Table-Top or Shelf MountingStop Preparation for Installing and Removing PMs1a Removing Chassis Cover Remove Chassis CoverConnector socket Installing PM Cards in the MagnumSlot. Align Removing PM Cards 2b Inserting PM Cards into a MagnumPM Cards 10a Removing Chassis Cover 10.1a Top View SPM Module Installed in a Installing an SPM Module in the MagnumRemoving an SPM Bonus Port Module Powering the MagnumRemove retaining screws for the SPM, face-plate only Remove SPM CardMagnum 8000X Mixed-Media Fiber Hubs Repeater Functionality OperationDual-Speed Functionality 8000X Dual-Speed Hub Functionality Address Learning Address Table MaintenanceThroughput Increase Auto-negotiation and speed-sensing Software TransparencyAuto-negotiation per-port for dual-speed hubs occurs when Chassis LEDs’cvr Power Budget Calculations for 8000X FPM’s and Fiber MediaIntroduction Magnum 8000X Port Modules FPM-MSC 100Mbps multi-mode FX-SC-type, snap-in connector FPM-MST, 100Mbps multi-mode FX-ST-type, twist-lock connectorActivity 2 Link FPM-SSC 100Mbps single-mode FX-SC-type, snap-in connector100BASE-FX MT-RJ ConnectorActivity Link SX short wavelength FPM-SXMST and Sxmsc 100BASE-SX when availablePM-RJ45 and RJ45U Twisted Pair PM-FP Must be installedEach empty PM slot Before Calling for Assistance TroubleshootingReturn Material Authorization RMA Procedure When Calling for AssistanceShipping and Packaging Information No Problem FoundB3.0 Applications for DC Powered Ethernet Hubs Specifications for Magnum Mixed -MEDIA 8000X HubsB4.1 UL Requirements B4.0 InstallationOperation B5.0B6.0 Ordering Information B7.0C5.0 Installation C4.0 Features and Benefits of the DUAL-SOURCE DesignC3.0 DUAL-SOURCE OPTION, Theory of Operation C6.0 Ordering Information C5.1 UL RequirementsExample Magnum 8000X-48VDC C7.0

8000X specifications

The GarrettCom 8000X series represents a significant advancement in industrial networking technology, designed specifically for demanding environments that require robust and reliable communication solutions. Known for its versatility and resilience, the 8000X series caters to various industries, including transportation, utilities, and automation, making it a go-to choice for mission-critical applications.

One of the main features of the 8000X is its modular design, allowing users to customize the switch according to their specific networking needs. This feature provides the flexibility to add and remove modules seamlessly, ensuring that the network can adapt as requirements change over time. The modularity also contributes to easier maintenance and upgrades, reducing downtime and enhancing operational efficiency.

The 8000X series is built to operate in harsh environments, with an operating temperature range of -40°C to 85°C, making it suitable for outdoor and industrial applications. Its rugged chassis is designed to withstand vibration and shock, ensuring reliability even in the most challenging conditions.

Equipped with both Ethernet and fiber optic ports, the 8000X series supports a variety of network topologies and facilitates extensive connectivity options. It usually offers multiple gigabit Ethernet ports, allowing for high-speed data transmission. This feature is crucial for applications that demand real-time data processing, such as video surveillance and process control systems.

In terms of security, the GarrettCom 8000X series incorporates advanced features such as VLAN support, access control lists (ACLs), and network monitoring tools. These security measures are essential for protecting sensitive data and maintaining network integrity against potential threats.

The device also supports various network protocols, including IPv4, IPv6, and various industrial protocols such as Modbus. This compatibility ensures that the 8000X can seamlessly integrate into existing infrastructures and communicate effectively with other devices and systems.

Furthermore, the GarrettCom 8000X series is equipped with built-in redundancy features, such as dual power supplies and support for Rapid Spanning Tree Protocol (RSTP), which enhance network reliability and minimize the risk of downtime.

Overall, the GarrettCom 8000X series stands out with its robust construction, modularity, and advanced technology, making it an ideal solution for organizations seeking reliable networking equipment capable of performing under extreme conditions. Its features make it a vital asset for industries focused on maintaining high-performance communication standards.