GE GEH6505A manual Modbus Equivalent Addresses, Power Leader EPM

Page 11

POWER LEADER™ Ethernet Gateway

Chapter 2 – Installation

manual) to record the devices attached to each network and verify that each device on each network has a unique address.

3.Modbus Concentrators may be used to add

POWER LEADER commnet devices to a Modbus network. The Concentrator assigns a Modbus-equivalent address to each commnet device attached to it. See Section 2-7 for a discussion of commnet and Modbus-equivalent addresses.

NOTE: While Modbus Concentrators are counted as regular Modbus devices, the commnet devices attached to Modbus Concentrators do NOT count toward the 31 device/network limit, but ARE considered in the 247 address/network limit.

4.No connections between Modbus networks are permitted, either directly or through repeaters.

5.Modbus networks are constrained to a maximum 4,000 feet of communication cable without repeaters.

6.RS485 repeaters may be used to extend the wiring length of a Modbus network or to provide isolation between runs of cable in a

Modbus network. Refer to GEH-6502 for appropriate wiring lengths with repeaters.

2–7 Modbus Equivalent Addresses

A maximum of 31 Modbus devices can be supported on a single RS485 network of the Ethernet Gateway. However, the Modbus RTU protocol permits up to 247 individual addresses to be recognized. These additional 216 addresses may be utilized by commnet devices attached to a special Modbus device, the Modbus Concentrator.

Commnet is a communications protocol utilized by many of the devices from GE’s POWER LEADER family of power management devices. The Modbus Concentrator is a Modbus RTU device that permits commnet devices to be assigned Modbus-equivalent addresses. Each Modbus Concentrator keeps track of up to 32 commnet devices and directs traffic between the Modbus network and the commnet

devices. To the Modbus network, the commnet devices appear as valid Modbus addresses.

To provide seamless integration of commnet- compatible devices into the Modbus RTU network, the Concentrator directly maps commnet addresses to equivalent Modbus addresses. The valid range of commnet addresses recognized by the concentrator is 300–514. These addresses are one-to-one mapped to the equivalent Modbus address range of 33–247.

For a more detailed discussion of commnet devices and the function of the Modbus Concentrator, see GEH-6491, the Modbus Concentrator Users Guide.

Table 4 lists commnet devices supported by the Modbus Concentrator (and the Ethernet Gateway).

Device

Description

 

 

POWER LEADER EPM

Full-function, three-phase electronic

 

meter with optional pulse initiation;

 

simple retrofit to existing

 

electromechanical installations. See

 

GEH–6302 for a full description.

 

 

POWER LEADER Meter

Full-function three-phase meter with

 

optional protective relaying and

 

waveform capture. See GEH–5892.

 

 

POWER LEADER MDP

Three-phase and ground protection

Overcurrent Relay

against overloads and rapid

 

detection of short circuits.

 

See GEK–100682.

 

 

Spectra ECM™

Advanced motor protection in full-

 

voltage-nonreversing (FVNR) and

 

full-voltage-reversing (FVR)

 

combination starter applications.

 

See GEH–6435.

MicroVersaTrip PM™ trip

Overcurrent protection and optional

unit in Spectra RMS™

full-function metering and protective

molded-case circuit

relaying. See GEH–5934.

breakers

 

 

 

MicroVersaTrip PM™ trip

Overcurrent protection and optional

unit in AKR, Power

full-function metering and protective

Break® and Power

relaying. See GEH–6273.

Break® II insulated-case

 

circuit breakers.

 

Table 4. POWER LEADER commnet devices supported by the

Modbus Concentrator.

7

Image 11
Contents Ethernet Gateway User’s Guide Power LeaderAS Used in this Publication Table of Contents Table of Contents Introduction Overview IntroductionHDD Physical DescriptionMessage Format Operational DescriptionEnvironmental Requirements Specifications TerminologyEthernet Connection InstallationInstallation Mounting Control Power ConnectionsWiring Rules Modbus Networks Modbus Connection Diagnostic ConnectionModbus Equivalent Addresses Power Leader EPMConfiguration Procedure ConfigurationConfiguration Ethernet Gateway IP Address Baud Rate SpecificationEthernet Driver Message MonitoringDisplay Socket, IP Address and Subnet Mask Gateway DiagnosticsNetwork Test Factory USE only Advanced Options Technical Support Personnel onlyOperation OperationDiagnostic Messages and Errors Monitor Mode Errors and Diagnostic MessagesTroubleshooting Guide Troubleshooting GuideRS485 Port Configuration Worksheets Configuration WorksheetsRS485 Port 2 Worksheet Baud Rate for RS485 Port RS485 Port 3 Worksheet Baud Rate for RS485 Port RS485 Port 4 Worksheet Baud Rate for RS485 Port GE Electrical Distribution & Control