POWER LEADER™ Ethernet Gateway
Chapter 2 – Installation
manual) to record the devices attached to each network and verify that each device on each network has a unique address.
3.Modbus Concentrators may be used to add
POWER LEADER commnet devices to a Modbus network. The Concentrator assigns a
NOTE: While Modbus Concentrators are counted as regular Modbus devices, the commnet devices attached to Modbus Concentrators do NOT count toward the 31 device/network limit, but ARE considered in the 247 address/network limit.
4.No connections between Modbus networks are permitted, either directly or through repeaters.
5.Modbus networks are constrained to a maximum 4,000 feet of communication cable without repeaters.
6.RS485 repeaters may be used to extend the wiring length of a Modbus network or to provide isolation between runs of cable in a
Modbus network. Refer to
2–7 Modbus Equivalent Addresses
A maximum of 31 Modbus devices can be supported on a single RS485 network of the Ethernet Gateway. However, the Modbus RTU protocol permits up to 247 individual addresses to be recognized. These additional 216 addresses may be utilized by commnet devices attached to a special Modbus device, the Modbus Concentrator.
Commnet is a communications protocol utilized by many of the devices from GE’s POWER LEADER family of power management devices. The Modbus Concentrator is a Modbus RTU device that permits commnet devices to be assigned
devices. To the Modbus network, the commnet devices appear as valid Modbus addresses.
To provide seamless integration of commnet- compatible devices into the Modbus RTU network, the Concentrator directly maps commnet addresses to equivalent Modbus addresses. The valid range of commnet addresses recognized by the concentrator is
For a more detailed discussion of commnet devices and the function of the Modbus Concentrator, see
Table 4 lists commnet devices supported by the Modbus Concentrator (and the Ethernet Gateway).
Device | Description |
|
|
POWER LEADER EPM | |
| meter with optional pulse initiation; |
| simple retrofit to existing |
| electromechanical installations. See |
| |
|
|
POWER LEADER Meter | |
| optional protective relaying and |
| waveform capture. See |
|
|
POWER LEADER MDP | |
Overcurrent Relay | against overloads and rapid |
| detection of short circuits. |
| See |
|
|
Spectra ECM™ | Advanced motor protection in full- |
| |
| |
| combination starter applications. |
| See |
MicroVersaTrip PM™ trip | Overcurrent protection and optional |
unit in Spectra RMS™ | |
relaying. See | |
breakers |
|
|
|
MicroVersaTrip PM™ trip | Overcurrent protection and optional |
unit in AKR, Power | |
Break® and Power | relaying. See |
Break® II |
|
circuit breakers. |
|
Table 4. POWER LEADER commnet devices supported by the
Modbus Concentrator.
7