POWER LEADER™ Ethernet Gateway

Chapter 1 – Introduction

Chapter 1 – Introduction

1–1 Overview

The GE POWER LEADER™ Ethernet Gateway (catalog number PLENETG01), shown in Figure 1, is a microprocessor-based device that connects one to four RS485-based Modbus Remote Terminal Unit (RTU) networks to an industry-standard, high- speed Ethernet network. Up to 31 Modbus RTU devices can be connected to each of the Modbus RTU networks.

Figure 1. POWER LEADER Ethernet Gateway.

The Ethernet Gateway works with GE’s Power

Management Control System (PMCS), a

comprehensive power management software platform that acts as the ‘host’ to RS485 networks attached to the Ethernet Gateway. A special part of the PMCS called the Dynamic Data Exchange (DDE) server is a database that records the

addresses and configurations of all attached devices. The Ethernet Gateway serves as a pass-

through device, interpreting the addressing information and routing queries from the host to the Modbus RTU networks and passing answers to those queries from the attached devices back to the host.

The Ethernet Gateway strictly conforms to the Modbus RTU protocol, providing the capability to tie the supported Modbus RTU devices into an Ethernet network. Table 1 contains a partial list of devices that are compatible with the Ethernet

Gateway and conform to the Modbus RTU standard.

Device

Description

 

 

EPM 3710

Full-function, three-phase electronic

 

meter with optional pulse initiation,

 

waveform capture, data logging, and

 

protective relay outputs.

EPM 3720

Full-function, three-phase electronic

 

meter with optional pulse initiation,

 

waveform capture, data logging,

 

protective relay outputs, and harmonic

 

distortion measurements.

Multilin 269 Plus

Protection for medium-voltage

Motor Management

industrial motors and associated

Relay

mechanical systems.

Multilin 565 Feeder

Complete time-overcurrent phase and

Management Relay

ground protection by monitoring feeder

 

phase current and ground current.

Fanuc 90/30 PLC

Programmable logic controller (PLC)

 

for applications from simple relay

 

replacement to midrange process

 

control.

Fanuc 90/70 PLC

Programmable logic controller with

 

multiple processors and programming

 

capabilities for large, high-speed

 

applications.

Modbus

Maps addresses of up to 32 attached

Concentrator

POWER LEADER communications

 

network (commnet) devices to

 

equivalent Modbus addresses for use

 

with the Ethernet Gateway.

Table 1. Examples of Modbus RTU compatible devices.

NOTE: PMCS is certified for use with power management components manufactured 5/13/96 or later. If your system interfaces to: 1) any trip units, meters, or relays manufactured prior to 5/13/96, or 2) any Spectra RMS™ Circuit Breakers with MicroVersaTrip PM™ Trip Units, please contact the POWER LEADER Customer Support Center at 1-800-843-3742.

As mentioned in Table 1, the Modbus Concentrator allows integration of POWER LEADER commnet devices with Modbus RTU-compatible networks for use with the Ethernet Gateway. See Section 3–5 for more details on the integration of commnet devices into Modbus networks.

Figure 2 illustrates a typical Modbus RTU network connected to a high-speed Ethernet through an Ethernet Gateway.

1

Image 5
Contents Ethernet Gateway User’s Guide Power LeaderAS Used in this Publication Table of Contents Table of Contents Introduction Overview IntroductionHDD Physical DescriptionMessage Format Operational DescriptionEnvironmental Requirements Specifications TerminologyInstallation Mounting InstallationControl Power Connections Ethernet ConnectionWiring Rules Modbus Networks Modbus Connection Diagnostic ConnectionModbus Equivalent Addresses Power Leader EPMConfiguration Procedure ConfigurationConfiguration Ethernet Gateway IP Address Baud Rate SpecificationEthernet Driver Message MonitoringDisplay Socket, IP Address and Subnet Mask Gateway DiagnosticsNetwork Test Factory USE only Advanced Options Technical Support Personnel onlyOperation OperationDiagnostic Messages and Errors Monitor Mode Errors and Diagnostic MessagesTroubleshooting Guide Troubleshooting GuideRS485 Port Configuration Worksheets Configuration WorksheetsRS485 Port 2 Worksheet Baud Rate for RS485 Port RS485 Port 3 Worksheet Baud Rate for RS485 Port RS485 Port 4 Worksheet Baud Rate for RS485 Port GE Electrical Distribution & Control