POWER LEADER™ Ethernet Gateway
Chapter 1 – Introduction
Chapter 1 – Introduction
1–1 Overview
The GE POWER LEADER™ Ethernet Gateway (catalog number PLENETG01), shown in Figure 1, is a
Figure 1. POWER LEADER Ethernet Gateway.
The Ethernet Gateway works with GE’s Power
Management Control System (PMCS), a
comprehensive power management software platform that acts as the ‘host’ to RS485 networks attached to the Ethernet Gateway. A special part of the PMCS called the Dynamic Data Exchange (DDE) server is a database that records the
addresses and configurations of all attached devices. The Ethernet Gateway serves as a pass-
through device, interpreting the addressing information and routing queries from the host to the Modbus RTU networks and passing answers to those queries from the attached devices back to the host.
The Ethernet Gateway strictly conforms to the Modbus RTU protocol, providing the capability to tie the supported Modbus RTU devices into an Ethernet network. Table 1 contains a partial list of devices that are compatible with the Ethernet
Gateway and conform to the Modbus RTU standard.
Device | Description |
|
|
EPM 3710 | |
| meter with optional pulse initiation, |
| waveform capture, data logging, and |
| protective relay outputs. |
EPM 3720 | |
| meter with optional pulse initiation, |
| waveform capture, data logging, |
| protective relay outputs, and harmonic |
| distortion measurements. |
Multilin 269 Plus | Protection for |
Motor Management | industrial motors and associated |
Relay | mechanical systems. |
Multilin 565 Feeder | Complete |
Management Relay | ground protection by monitoring feeder |
| phase current and ground current. |
Fanuc 90/30 PLC | Programmable logic controller (PLC) |
| for applications from simple relay |
| replacement to midrange process |
| control. |
Fanuc 90/70 PLC | Programmable logic controller with |
| multiple processors and programming |
| capabilities for large, |
| applications. |
Modbus | Maps addresses of up to 32 attached |
Concentrator | POWER LEADER communications |
| network (commnet) devices to |
| equivalent Modbus addresses for use |
| with the Ethernet Gateway. |
Table 1. Examples of Modbus RTU compatible devices.
NOTE: PMCS is certified for use with power management components manufactured 5/13/96 or later. If your system interfaces to: 1) any trip units, meters, or relays manufactured prior to 5/13/96, or 2) any Spectra RMS™ Circuit Breakers with MicroVersaTrip PM™ Trip Units, please contact the POWER LEADER Customer Support Center at
As mentioned in Table 1, the Modbus Concentrator allows integration of POWER LEADER commnet devices with Modbus
Figure 2 illustrates a typical Modbus RTU network connected to a high-speed Ethernet through an Ethernet Gateway.
1