Section 1 — General Information
ATS “HS” Type Transfer Switch
1.1INTRODUCTION
This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect appli- cation, or improper procedures.
Every effort has been expended to make sure that the contents of this manual are both accurate and cur- rent. The manufacturer, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.
Figure 1.1 — Typical ATS Transfer Mechanism
UTILITY LUGS
UTILITY
CLOSING
COIL
GENERATOR
LUGS (E1 & E2)
GENERATOR
CLOSING
COIL
1.2EQUIPMENT DESCRIPTION
The automatic transfer switch is used for transfer- ring electrical load from a UTILITY (NORMAL) power source to an EMERGENCY (STANDBY) power source. Such a transfer of electrical loads occurs automati- cally when the UTILITY power source has failed or is substantially reduced and the EMERGENCY source voltage and frequency have reached an acceptable level. The transfer switch prevents electrical feedback between two different power sources (such as the UTILITY and EMERGENCY sources) and, for that reason, codes require it in all standby electric system installations.
The transfer switch consists of a transfer mecha- nism, service disconnect circuit breaker, a relay control, fuses, and a terminal strip for connection of sensing wires.
This transfer switch is suitable for use as service entrance equipment.
1.2.1 TRANSFER SWITCH MECHANISM
These switches (Figure 1.1) are used with a single- phase system, when the
Solderless,
Switch | Wire | Conductor Tightening |
Rating | Range | Torque |
100A | 50 | |
200A | 275 |
This transfer switch is suitable for control of motors, electric discharge lamps, tungsten filament and elec- tric heating equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.
LOAD LUGS (T1 & T2)
This transfer switch is for use in optional standby systems only.
This transfer switch is suitable for use on a circuit capable of 10,000 rms symmetrical amperes, 240 VAC maximum.
1.2.2 SERVICE DISCONNECT CIRCUIT BREAKER
The service disconnect circuit breaker for the 100 amp models are:
•Siemens, Type BQ,
•120/240VAC, 100A
•50/60 Hertz
•Heating, Air Conditioning and Refrigeration (HACR) rated
•Wire range: #1 - #8 AWG.
•The conductor tightening torque is 50
The service disconnect circuit breaker for the 200 amp models are:
•Siemens, Type QN,
•120/240VAC, 200A
•50/60 Hertz
•Heating, Air Conditioning and Refrigeration (HACR) rated
•Wire range: 300 KCMIL - 4 AWG
•The conductor tightening torque is 250
1.3TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.
2