Eaton Electrical 3105 UPS manual LED & Alarm Status Table, Specification

Page 10

LED & Alarm Status Table

UPS status

 

Green LED

Red LED

Buzzer

 

 

 

 

 

 

Self test

 

Blink 1 (by turns)

B1

 

 

 

 

 

 

 

 

Charging

ON

OFF

OFF

 

 

 

 

 

 

AC (Utility mode

 

Charge off

ON

OFF

OFF

 

 

 

 

 

 

Low battery

ON

Blink 2

B5

 

 

 

 

 

 

 

 

 

 

Over load

ON

Blink 2

B4

 

 

 

 

 

 

 

 

Normal

Blink 2

OFF

B1

DC (Battery

 

 

 

 

 

 

Over load

Blink 2

OFF

B1

Mode)

 

 

 

 

 

 

 

 

Low battery

Blink 2

Blink 2

B3

 

 

 

 

 

Short/Fault/DC Over-Bat

OFF

ON

ON

 

 

 

 

 

AC Over-Bat/Bat Fault

 

OFF

Blink 2

B5

 

 

 

 

 

 

Notes:

Blink 1: ON 0.5 seconds / OFF 0.5 seconds

Blink 2: ON 0.25 seconds / OFF 0.25 seconds

B1: 1 beep / 5 seconds ON 0.25 seconds / OFF 4.75 seconds

B3: 2 beeps / 5 seconds ON, 0.25 seconds / OFF 0.25 seconds 2 times 4 seconds OFF

B4: ON 0.5 seconds / OFF 0.5 seconds

B5: 3 beeps / 5 seconds ON 0.25 seconds / OFF 0.25 seconds 3 times 3.5 seconds OFF

Specification*:

Rating

350VA

500VA

700VA

Part Number

31050350A

31050500A

31050700A

Capacity

350VA/210W

500VA/300W

700VA/420W

Dimensions (mm) HxWxD

180x280x115

180x280x115

180x280x115

Unit Weight (kg)

4.5

5

6.5

Input Connection

1.8 metre line cord IEC to Australian 10Amp Plug

Output Connection

6 Australian 10Amp Outlets (3 Battery Backup & Surge Protection,

 

 

3 Surge Protection only)

 

Operation

 

 

 

Input Voltage Range

 

0-300 VAC

 

Output Voltage Range

 

Nominal -18% to +10%

 

On Battery Output Voltage

 

Nominal -12% to +10%

 

Frequency

 

50 Hz

 

Lightning/Surge Protection

 

476 joules

 

Safety

 

AS/NZS62040.1.1, AS/NZS60950, A-Tick

EMI

 

AS/NZS62040.2, AS/NZSCISPR22, C-Tick

Transfer Time to Battery/AC

 

2-6 msec. typical

 

Battery Type

 

Sealed, maintenance free lead-acid battery

Typical Backup Time

 

3 minutes at full rated load

Internet/Phone/Fax Protection

 

RJ11

 

Short Circuit Protection

 

Circuit Breaker

 

Communication Port

 

USB

 

Environmental

 

 

 

Operation Temperature

 

0oC - 40oC

 

Operation Relative Humidity

 

0 to 95% non condensing

 

Storage Temperature

 

-15oC - 50oC

 

Software

Powerware LanSafe Software is included free of charge

Service Plans

Optional Extended Warranty and On Site Changeover service plans available

*Due to continuing product improvement programs, specifications subject to change without notice

10

UserÊs Manual 350-700VA Rev B

Image 10
Contents Powerware 3105 UPS UserÊs manual UserÊs Manual 350-700VA Rev B Contents Introduction FeaturesUnit inspection Safety Instructions Connecting the Battery Battery connection required before useInstallation and Operation Indicators On/Off Push Button/Test SwitchBattery Replacement procedure RJ11 Phone/Fax Protection Connectors USB Communication PortStatus Indicators LED & Alarm Status Table SpecificationTroubleshooting Service and SupportPowerware National Service Centre 1300 303 Head Office Sales Offices