CyberPower Systems CPS1500AVR user manual Troubleshooting, Specifications

Page 16

TROUBLESHOOTING

Problem

Possible Cause

Solution

Outlets do not provide

Circuit breaker is tripped due

Turn the UPS off and unplug at least one

power to equipment

to overload

piece of equipment. Wait 10 seconds, reset

 

 

the circuit breaker and then turn the UPS on.

 

Batteries are discharged

Allow the unit to recharge for at least 4 hours.

 

Unit has been damaged by a

Contact CyberPower Systems at

 

surge or spike.

tech@cyberpowersystems.com

The UPS does not

Batteries are not fully charged.

Recharge the battery by leaving the UPS

perform expected runtime.

 

plugged in.

 

Batteries are worn out.

Contact CyberPower Systems at

 

 

tech@cyberpowersystems.com

The UPS will not turn on.

The on/off switch is designed to

Turn the UPS off. W ait 10 seconds and then

 

prevent damage by rapidly

turn the UPS on.

 

turning it off and on.

 

 

The unit is not connected to an

The unit must be connected to a 110/120v outlet.

 

AC outlet.

 

 

The batteries are worn out.

Contact CyberPower Systems at

 

 

tech@cyberpowersystems.com

 

Mechanical problem.

Contact CyberPower Systems at

 

 

tech@cyberpowersystems.com

PowerPanel Plus™ is

The serial cable is not connected.

Connect the serial cable to the UPS unit and an

inactive (all icons are gray).

 

open serial port on the back of the computer.

 

 

You must use the cable that came with the unit.

 

The serial cable is connected to

The primary computer must be connected to

 

the wrong port.

Port I on the UPS. Check the bac k of the

 

 

computer for a different serial port. Move the

 

 

cable to this port.

 

The unit is not providing battery

Turn the UPS off. W ait 10 seconds and then

 

power.

turn the UPS on. This should reset the unit.

 

The serial cable is not the cable

You must use the cable that came with the unit.

 

that was provided with the unit.

 

SPECIFICATIONS

 

 

General

Input

UPS- Output

Battery

Interface

 

Model

CPS1500AVR

 

Capacity

1500AV (950W)

 

Frequency

47Hz - 63Hz

 

 

Voltage Range

85v - 150v

 

Line Conditioning Regulation

AVR Max. boost 15% of input voltage for output regulation

 

 

 

while input voltage is from 8% to 30% under nominal

 

 

AVR Max. buck 15% of input voltage for output regulation

 

 

while input voltage is from 8% to 26% over nominal

 

On Battery Output Voltage

120 Vac ÿ±5% (user adjustable)

 

Transfer Time

4ms typical, including detection time

 

On Battery Output Wave Form

Simulated Sine Wave Form

 

Max. Load

1500VA (950W)

 

Battery Type

Sealed, maintenance-free lead acid battery

 

 

Number of Batteries

12v/7AH x 4

 

Recharge Time

4 to 8 hours from total discharge

 

Communication

RS-232 with Plug and Play interface

 

 

LED Indicators

Power On, Electrical Wiring Fault, AVR, Using Battery,

 

 

Battery Charge Level, Load Level

 

Ouput Receptacles

6 Battery-powered and full-time surge protection

14

Image 16
Contents Additional Installation Tips can be Found AT Table of Contents CPS1500AVR Hardware Installation Guide HOW to Determine the Power Requirements of Your EquipmentInspection Software Installation Information Powerpanel Plustm Software Installation Guide For Windows 95/98/MeFor Windows For Windows NTPowerPanel PlusTM Main Menu Powerpanel Plustm Main Window Description Powerpanel Plustm Setup WindowPowerpanel Plustm Advanced Setup Powerpanel Plustm Schedule MenuPowerpanel Plustm LOG Menu Powerpaneltm Installation GuideFor Windows 95/98/ME For Windows NT Testing Your UPS System Replacing the Battery To Replace the BatteryDefinitions for LED Indicators AVRTroubleshooting SpecificationsRegistration Limited Warranty Power Control Guarantee Limitation may not apply to you Mailsales@cyberpowersystems.com