CyberPower Systems CPS1500AVR user manual Definitions for LED Indicators, Avr

Page 15

CPS1500AVR

Guaranteed Uninterruptible Power System

DEFINITIONS FOR LED INDICATORS

 

Power On

Wiring

AVR

Using

Circuit

Alarm

Condition

 

 

 

Fault

 

Battery

Breaker

 

 

 

On

Off

Off

Off

Set

Off

Normal

 

On

Off

Flash

Off

Set

Off

AVR - Max. boost 15% of input voltage for output regulation

 

 

 

 

 

 

 

while input voltage is from 8% to 30% under nominal.

 

On

Off

On

Off

Set

Off

AVR - Max. buck 15% of input voltage for output regulation

 

 

 

 

 

 

 

while input voltage is from 8% to 26% over nominal.

 

Off

On/Off

Off

On

Set

Two Beeps

Utility Failure - The UPS is providing battery power to the

 

 

 

 

 

 

 

battery outlets.

 

Off

On/Off

Off

On

Set

Rapid Beeps

Utility Failure - The UPS is providing battery power to the

 

 

 

 

 

 

 

battery outlets. Rapid beeps indicate that the battery will run

 

 

 

 

 

 

 

out of charge within a few minutes.

 

On/Off

On/Off

On/Off/Flash

On/Off

Set

Long Beep

Overload - Turn the UPS off and unplug at least one piece of

 

 

 

 

 

 

 

equipment. Wait 5 seconds, reset the circuit breakers and

 

 

 

 

 

 

 

restart the UPS.

 

Off

Off

Off

On

Up

Long Beep

Overload - Turn the UPS off and unplug at least one piece of

 

 

 

 

 

 

 

equipment. Wait 5 seconds, reset the circuit breakers and

 

 

 

 

 

 

 

restart the UPS.

 

Off

Off

Off

Off

Set

Off

Surge Protection Malfunction - Power surge has damaged

 

 

 

 

 

 

 

the unit. Please contact CyberPower Systems.

 

On/Off

On/Off

On/Off/Flash

On/Off

Set/Up

None

Electrical Wiring Fault - Indicates a wiring problem such as a

 

 

 

 

 

 

 

bad ground, missed ground or reversed wiring within the AC

 

 

 

 

 

 

 

outlet. User is advised to disconnect all equipment from the

 

 

 

 

 

 

 

outlet and have it checked by an electrician.

The load indicator LED will turn red if the load is between 80 and 100%.

If the load or battery charge is under 20%, no indicator LED will illuminate.

13

Image 15
Contents Additional Installation Tips can be Found AT Table of Contents CPS1500AVR HOW to Determine the Power Requirements of Your Equipment Hardware Installation GuideInspection Software Installation Information For Windows 95/98/Me Powerpanel Plustm Software Installation GuideFor Windows NT For WindowsPowerPanel PlusTM Main Menu Powerpanel Plustm Setup Window Powerpanel Plustm Main Window DescriptionPowerpanel Plustm Schedule Menu Powerpanel Plustm Advanced SetupPowerpaneltm Installation Guide Powerpanel Plustm LOG MenuFor Windows 95/98/ME For Windows NT Testing Your UPS System To Replace the Battery Replacing the BatteryAVR Definitions for LED IndicatorsSpecifications TroubleshootingRegistration Limited Warranty Power Control Guarantee Limitation may not apply to you Mailsales@cyberpowersystems.com