B&B Electronics DTB Series user manual Operation

Page 4

6

Operation

There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation mode.

Press the

key to switch to regulation mode. If the

key is pressed for more than 3 seconds, controller will switch to the initial setting

mode. Pressing the

key while in the regulation mode or initial setting mode, forces the controller to return to the operation mode.

PV/SV: Sets the temperature set point and displays the temperature process value. Use

keys to set the temperature set point.

Setting method: While in any function mode, press the

key to select the desired function and use the

keys to change settings.

 

Press

key to save the changes.

 

 

 

The next flow chart shows how to switch for settings and internal functions:

Regulation Mode

Press key less than 3 sec

Press key

Operation Mode

Press key more than 3 sec

Press key

Initial Setting Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regulation Mode

 

 

 

 

 

 

 

 

 

 

 

Operation Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto-tuning

 

 

 

 

 

 

 

Use

key to

 

(Set in PID control and RUN mode)

 

 

set temperature set point

 

Press

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 groups PID modes (n=0~3). When n=4,

 

 

 

 

 

 

Control setting RUN or STOP

 

 

 

 

 

 

 

 

 

PID control is auto regulated.

 

Press

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PD control offset

 

 

 

 

Start pattern setting (PID

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

program control and

 

(When PID control is ON and Ti=0,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time setting.

 

set the value of PdoF.

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

Press

 

 

 

 

 

Heating hystereisis setting

 

 

 

 

 

 

Decimal point position selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(except for B, S, R type, all the

 

(Set in ON/OFF control mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

other types can be set)

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling hystereisis setting

 

 

 

 

 

 

 

Upper-limit alarm 1

 

 

 

 

 

 

 

 

 

 

 

 

 

(Set in ON/OFF control mode)

 

(This

parameter is available only when

 

Press

 

 

 

 

 

 

 

ALA1 function enables)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or

 

Heating/Cooling

 

 

 

 

 

 

 

Lower-limit alarm 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control cycle setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(This parameter is available only when

 

(Set in PID control mode)

 

 

Press

 

 

 

 

 

 

 

ALA1 function enables)

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control cycle setting

 

 

 

 

 

 

 

Upper-limit alarm 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of 2nd output group

 

 

 

 

 

 

 

 

 

 

 

 

 

(This parameter is available only when

 

(Set in PID control and Dual Loop

 

 

 

 

ALA2 function enables)

 

output control mode)

 

 

 

 

 

Press

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P value of 1st & 2nd output grou

 

 

 

 

 

 

 

Lower-limit alarm 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

during dual loop output control

 

 

 

 

 

 

 

 

 

 

(This parameter is available only when

 

P value of 2nd output group =

 

 

 

 

ALA2 function enables)

 

(P value of 1st output group) x

 

 

 

 

 

 

 

 

 

Press

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dead Band (Set in Dual Loop

 

 

 

 

 

 

Upper-limit alarm 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output control mode)

 

 

 

 

 

 

 

 

 

 

 

 

(This parameter is available only when

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALA3 function enables)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

Switch setting for feedback

 

 

 

 

 

 

Lower-limit alarm 3

 

 

 

 

 

 

 

 

 

 

 

 

signal of valve. (Display when

 

(This parameter is available only when

 

valve control is ON)

 

 

ALA3 function enables)

 

Press

 

 

 

 

 

 

 

Press

 

 

 

 

 

 

 

Automatically regulate

 

 

 

 

Setting lock mode

 

 

 

 

 

 

 

 

 

 

 

 

 

feedback value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Display when valve control is ON)

 

 

Press

 

 

 

Press

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initial Setting Mode

Set input type

Press

Set temperature unit do not display when analog input

Press

Set upper-limit of

temperature range Press

Set lower-limit of

temperature range

Press

Select control mode

(See "Pattern and set Editing selection" for detail)

Press

Select heating/cooling control

or dual loop output control Press

Alarm 1 mode setting Press

Alarm 2 mode setting Press

Alarm 3 mode setting Press

Set system alarm

Press

Communication write function

enable/disable Press

3

Image 4
Contents DTB Series Precaution Display, LED and PushbuttonsOrdering Information DTB SeriesSpecifications Temperature Sensor Type and Temperature RangeOperation Controller. Display when valve Signal feedback function is onWhen valve feedback Scale = 2.8uA = 1.3mV for tuning output valueDual Loop Output Control Heating / Cooling Control Key simultaneously, the Lock status can be releasedAlarm Outputs Alarm Type Alarm Output OperationCurrent Transformer CT Function Event Inputs FunctionPID Program Control Ramp/Soak Program Control PID ControlHysteresis setting value of the 2nd RS-485 Communication20BFH Pattern 0 time is set to 2080H~2087HTerminals Identification Panel Cutout and Terminals IdentificationDTB4848 External Dimensions DTB4824DTB4896 DTB9696Error Acknowledge and Display CT Wiring Method if CT function is selectedMounting Mounting Method

DTB Series specifications

B&B Electronics, a well-regarded player in the field of industrial communication technologies, has made a significant impact with its DTB Series of data transport bridges. Designed for robust data transmission, these devices address the needs of industries that require reliable and efficient communication solutions.

One of the standout features of the DTB Series is its capability to handle multiple communication protocols. This versatility allows users to connect devices operating under different standards without the need for multiple converters, simplifying integration within existing systems. Each model in the series supports various serial communication standards, including RS-232, RS-422, and RS-485, offering the flexibility to cater to a wide range of applications.

The DTB devices leverage advanced technologies to ensure high-speed data transmission. With support for data rates up to 115.2 kbps, they enable rapid communication across significant distances. This is particularly beneficial in settings where timely data exchange is critical, such as in manufacturing floors or utility management systems. Moreover, the devices are engineered to maintain data integrity, employing robust error-checking mechanisms and reliable power supply options.

Characteristically, the DTB Series is built for durability and longevity in demanding environments. The rugged housing of these devices provides protection against dust, moisture, and electromagnetic interference, which are common issues faced in industrial settings. This durability ensures that the DTB devices can perform consistently even in harsh conditions.

Additional features include LED indicators for monitoring power and communication status, which enhances user control and troubleshooting capabilities. With an easy-to-install design, the DTB Series allows for seamless integration into existing systems, reducing the time and effort required for setup.

Furthermore, the DTB Series embodies adaptive technology, supporting automatic configuration and a variety of mounting options, including DIN rail and panel mount installations, providing users with flexibility in deployment.

In conclusion, B&B Electronics' DTB Series stands out as a highly reliable solution for industrial data communication. Its combination of protocol versatility, high-speed performance, rugged construction, and user-friendly design makes it an ideal choice for industries seeking to enhance their communication infrastructure. Whether in factory automation, transportation, or utility management, the DTB Series provides the necessary tools to facilitate seamless and efficient data transport.