Citrix Systems 9.3 setup guide Preparing the Site and Rack, Site Requirements, Rack Requirements

Page 71

Citrix NetScaler Hardware Installation and Setup Guide

wA computer to serve as a management workstation

Preparing the Site and Rack

There are specific site and rack requirements for the NetScaler appliance. You must make sure that adequate environmental control and power density are available. Racks must be bolted to the ground, have sufficient airflow, and have adequate power and network connections. Preparing the site and rack are important steps in the installation process and help ensure a smooth installation.

Site Requirements

The appliance should be installed in a server room or server cabinet with the following features:

Environment control

An air conditioner, preferably a dedicated computer room air conditioner (CRAC), capable of maintaining the cabinet or server room at a temperature of no more than 21 degrees C/70 degrees F at altitudes of up to 2100 m/7000 ft, or 15 degrees C/60 degrees F at higher altitudes, a humidity level no greater than 45 percent, and a dust-free environment.

Power density

Wiring capable of handling at least 4,000 watts per rack unit in addition to power needs for the CRAC.

Rack Requirements

The rack on which you install your appliance should meet the following criteria:

Rack characteristics

Racks should be either integrated into a purpose-designed server cabinet or be the floor-to-ceiling type, bolted down at both top and bottom to ensure stability. If you have a cabinet, it should be installed perpendicular to a load-bearing wall for stability and sufficient airflow. If you have a server room, your racks should be installed in rows spaced at least 1 meter/3 feet apart for sufficient airflow. Your rack must allow your IT personnel unfettered access to the front and back of each server and to all power and network connections.

Power connections

At minimum, two standard power outlets per unit.

Network connections

71

Image 71 Contents
Citrix NetScaler Hardware Installation and Setup Guide Copyright and Trademark Notice Contents Preparing for Installation Lights Out Management Port of the NetScaler Appliance Contents Formatting Conventions Meaning Boldface Formatting Conventions for NetScaler DocumentationThis Preface To view the documentation Documentation Available on the NetScaler ApplianceConvention Meaning To provide feedback at the Knowledge Center home Getting Service and SupportNetScaler Documentation Feedback Preface Topics Introduction to the Hardware PlatformsStartup Screen Booting ScreenCommon Hardware Components LCD DisplayLCD Startup Screen Out-of-Service Screen LCD Http Statistics Screen Network Traffic Statistics Screen Http Statistics Screen10.Port Information for a 10-port Appliance Ports Row abbreviation/symbol Indicates1G SFP, 10G SFP+, and XFP Ports RS232 Serial PortCopper Ethernet Ports Management PortsPack Copper 1G SFP Distance SpecificationsShort Reach Fiber 1G SFP Distance Specifications 1G Pluggable MediaSingle GE Pluggable Media Long Reach Fiber 1G SFP Distance SpecificationsShort Reach Fiber 10G SFP+ Distance Specifications Short Reach XFP 10G Distance Specifications 11.Long Reach Fiber XFP 10G Distance Specifications 10.Long Reach Fiber 10G SFP+ Distance SpecificationsDescription Products LED Port-Status IndicatorsIntroduction to the Hardware Platforms Port Type LED Location LED Function LED Color LED Indicates Field Replaceable Units Power SupplyAmber Power Supply Type LED Color LED IndicatesReplacing an AC Power Supply Replacing a DC Power Supply CompactFlash Card 13.Removing the Existing DC Power SupplyReplacing a CompactFlash Card 15.Removing the Existing CompactFlash Card To replace a solid-state drive Solid-State Drive17.Removing the Existing Solid-State Drive Shutdown -p nowHard Disk Drive To install a hard disk drive19.Removing the Existing Hard Disk Drive Direct Attach Cable21.Inserting a DAC into the 10G port To install or remove a direct attach cableCitrix NetScaler 9010 Fips Hardware Platforms25.Citrix NetScaler 9010 Fips appliance, back panel Citrix NetScaler 12000-10G26.Citrix 12000-10G appliance, front panel 28.Citrix NetScaler MPX 5500, front panel Citrix NetScaler MPX29.Citrix NetScaler MPX 5500, back panel Citrix NetScaler MPX 5550 and MPX31.Citrix NetScaler MPX 5550/5650 appliance, back panel Citrix NetScaler MPX 7500 and MPX34.Citrix NetScaler MPX 7500/9500, back panel Citrix NetScaler MPX 8200, MPX 8400, MPX 8600, and MPX Introduction to the Hardware Platforms 38.Citrix NetScaler MPX 9700/10500/12500/15500, front panel Citrix NetScaler MPX 9700, MPX 10500, MPX 12500, and MPXIntroduction to the Hardware Platforms Page Introduction to the Hardware Platforms Citrix NetScaler MPX 44.Citrix NetScaler MPX 15000 appliance, front panel Citrix NetScaler MPX 47.Citrix NetScaler MPX 17000 appliance, back panel Citrix NetScaler MPX 17500, MPX 19500, and MPXCitrix NetScaler Hardware Installation and Setup Guide Citrix NetScaler MPX 17550, MPX 19550, MPX 20550, and MPX Citrix NetScaler Hardware Installation and Setup Guide Introduction to the Hardware Platforms 16.Standard Platform Summary Fips 12000-10G Summary of Hardware SpecificationsAse-T copper Fips 12000-10G17.MPX Platform Summary MPX 5550/MPX MPX 7500/MPX 5650 9500 8x10/100/1000BCitrix NetScaler Hardware Installation and Setup Guide Port model 6x10/100/1000 MPX MPX 5550/MPX MPX 7500/MPX 565018.MPX Platform Summary contd MPX 8200/MPX MPX 9700/MPX Ten network 6x1G SFP +Four network 2x10G SFP+ 10G and Fips MPX MPX 8200/MPX MPX 9700/MPX10G and Fips 2x10G SFP+ 6x10/100/1000 Base-T copper Ethernet modelUL & TUV-C CSA SFP+ model 19.MPX Platform Summary contd MPX 17500/MPXMPX 22040/MPX 12x1G SFP + 24x10GTUV CSA MPX Introduction to the Hardware Platforms Preparing for Installation Unpacking the Appliance Rack Requirements Preparing the Site and RackSite Requirements Space requirements Electrical Safety PrecautionsAppliance Precautions Rack Precautions Installing the Hardware Platform Number of rack units Rack Mounting the ApplianceTo attach the inner rails to the appliance To remove the inner rails from the rail assemblyAttaching inner rails To install the rack rails on the rackInstalling the Rail Assembly to the Rack To install the appliance in the rackRack Mounting the Appliance Installing and Removing 1G SFP TransceiversInstalling a 1G SFP transceiver To install a 1G SFP transceiverTo remove a 1G SFP transceiver Installing and Removing XFP and 10G SFP+ TransceiversTo install an XFP/10G SFP+ transceiver Locking an XFP transceiver To remove an XFP/10G SFP+ transceiverConnecting the Ethernet Cables Connecting the CablesTo connect the console cable to a computer or terminal Connecting the Console CableConnecting the Power Cable To connect the appliance to the power source Switching on the ApplianceTo switch on the appliance 11.Power switch on back panel Initial Configuration LCD Key Functions Using the LCD KeypadTo configure initial settings by using a serial console Using the NetScaler Serial ConsoleCitrix Application Firewall Reboot ExampleCitrix NetScaler Access Gateway Using the Setup WizardTo configure initial settings by using the Setup Wizard Using Dhcp for Initial Access Prerequisites Killall dhcpd dhcpd Sample Dhcp configuration dhcpd.confTo find the Snip address from the Dhcp server To find the Snip address from the NetScaler consoleUsing Dhcp When a Configuration File is Present Accessing a NetScaler by Using SSH Keys and No Password At the shell prompt, change the directory to /nsconfig/ssh Changing the Administrative Password Example Lights Out Management Port NetScaler Appliance To access the LOM by using a web browser Accessing the LOM Port by using a Web BrowserConfiguring the LOM Port To Configure the NetScaler LOM PortPerforming a Core Dump Power Cycling the ApplianceAccessing the Appliance by using the Access Console To power cycle the applianceTo obtain health monitoring information Obtaining Properties of the HostObtaining Health Monitoring Information Under Options, click Console RedirectionTo perform power control operations Power Control Operations using the LOM PortLights Out Management Port of the NetScaler Appliance 108 To migrate a configuration To migrate a configuration