Dell R220 owner manual 300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985

Page 80

Environmental

 

Six consecutively executed shock pulses in the positive and negative x, y, and

 

z axes (one pulse on each side of the system) of 32 G faired square wave

 

pulse with velocity change at 270 inches/second (686 centimeters/second).

Maximum Altitude

 

Operating

3048 m (10,000

Storage

12,000 m (39,370 ft).

Operating Altitude De-rating

≤ 35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m

 

(3,117 ft).

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.

Air Filtration

Conductive Dust

Corrosive Dust

Gaseous Contamination

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

NOTE: Applies to data center and non-data center environments.

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

NOTE: Applies to data center and non-data center environments.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less than 60% relative humidity.

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Copper Coupon

<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.

Corrosion Rate

 

Silver Coupon

<200 Å/month as defined by AHSRAE TC9.9.

Corrosion Rate

 

80

Image 80
Contents Dell PowerEdge R220 Page Contents Page Troubleshooting Your System Using System DiagnosticsJumpers And Connectors Technical Specifications System MessagesGetting Help Front-Panel Features And Indicators About Your SystemSee Getting Help Back-Panel Features And Indicators Back-Panel Features and IndicatorsNIC Indicator Codes Related DocumentationQuick Resource Locator Using The System Setup And Boot Manager Choosing The System Boot Mode Entering System SetupResponding To Error Messages Using The System Setup Navigation KeysSystem Bios Screen System Setup OptionsSystem Setup Main Screen Memory Settings Screen System Information ScreenProcessor Settings Screen Sata Settings ScreenBoot Settings Screen Integrated Devices ScreenTimer Serial Communications ScreenSystem Profile Settings Screen System Security ScreenMiscellaneous Settings Power ButtonSystem And Setup Password Features Assigning a System And/Or Setup PasswordDeleting Or Changing An Existing Setup Password Using Your System Password To Secure Your SystemUsing The Boot Manager Navigation Keys Entering The Uefi Boot ManagerOperating With a Setup Password Enabled Boot Manager Screen Uefi Boot MenuIDRAC Settings Utility Entering The iDRAC Settings UtilityChanging The Thermal Settings Embedded System ManagementInstalling System Components Installing The Front BezelRecommended Tools Front Bezel OptionalOpening And Closing The System Opening The SystemInside The System Closing The SystemChassis Intrusion Switch Removing The Chassis Intrusion SwitchRemoving The Optical Drive Installing The Chassis Intrusion SwitchOptical Drive Optional Installing The Optical Drive Removing and Installing the Optical DriveHard Drives Removing a 3.5 Inch Hard-Drive CageHard-drive cage Installing a 3.5 Inch Hard-Drive Cage Removing a 3.5 Inch Hard Drive From The Hard-Drive CageInstalling a 3.5 Inch Hard Drive Into The Hard-Drive Cage Removing a 2.5 Inch Hard-Drive CageInstalling a 2.5 Inch Hard-Drive Cage Removing and Installing a 2.5 Inch Hard-Drive CageInstalling a 2.5 Inch Hard Drive Into The Hard-Drive Cage Removing a 2.5 Inch Hard Drive From The Hard-Drive CageLED Module Removing The LED ModuleRemoving The Control-Panel Board Installing The LED ModuleControl-Panel Board Installing The Control-Panel Board Removing and Installing the Control-Panel BoardCooling Fans Removing a Cooling FanInstalling a Cooling Fan Removing and Installing a Cooling FanCooling Shroud Removing The Cooling ShroudInstalling The Cooling Shroud System MemoryGeneral Memory Module Installation Guidelines Sample Memory ConfigurationsRemoving Memory Modules Removing the Memory ModuleInstalling Memory Modules Removing And Installing The Internal USB Key Internal USB Memory Key OptionalExpansion Card Types And Form Factor Expansion Card Installation GuidelinesExpansion Cards And Expansion-Card Risers Removing and Installing the Expansion Card on the Riser Removing An Expansion CardInstalling An Expansion Card Removing The Expansion-Card RiserInstalling The Expansion-Card Riser Removing and Installing the Expansion-Card RiserIDRAC7 Enterprise Card Optional Removing The iDRAC7 Enterprise CardSystem Battery Installing The iDRAC7 Enterprise CardReplacing The System Battery Replacing the System BatteryProcessor Removing The ProcessorRemoving and Installing the Processor Heat Sink Installing The Processor Removing and Installing a ProcessorPower Supply Unit Removing The Power Supply UnitInstalling The Power Supply Removing and Installing the Power Supply UnitSystem Board Removing The System BoardInstalling The System Board Removing and Installing the System BoardPage Troubleshooting Your System Troubleshooting External ConnectionsTroubleshooting The Video Subsystem Troubleshooting a USB DeviceTroubleshooting a Serial I/O Device Troubleshooting a NICTroubleshooting a Wet System Troubleshooting a Damaged SystemTroubleshooting The System Battery Troubleshooting The Power SupplyTroubleshooting System Memory Troubleshooting Cooling ProblemsTroubleshooting Cooling Fans Troubleshooting An Internal USB Key Troubleshooting An SD Card Troubleshooting An Optical DriveTroubleshooting a Hard Drive Troubleshooting Expansion CardsTroubleshooting The Processor Using System Diagnostics Dell Embedded System DiagnosticsWhen To Use The Embedded System Diagnostics Running The Embedded System DiagnosticsDisplayed if at least one event description is recorded Jumpers And Connectors System Board Jumper SettingsSystem Board Connectors INTUSB1Disabling a Forgotten Password Technical Specifications UdimmUSB 300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985 Page System Error Messages System MessagesASR0003 Message CPU0023 Message CPU0703 Message FAN0001 Message MEM0007 Message PCI1302 Message PCI1360 Message SEC0033 Message Diagnostic Messages Alert MessagesLocating Your System Service Tag Getting HelpContacting Dell Documentation Feedback