FieldServer FS-8700-22 X30 instruction manual Map Descriptor Example

Page 9

FS-8700-22_X30_DeviceNet_Slave Manual

Page 9 of 12

4.4.3.Map Descriptor Example.

// Client side Map Descriptors

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

DeviceNet_Data_Type,

Address,

Length,

Scan_Interval

 

 

 

 

 

 

 

 

 

Get_Data,

Input_Data,

0,

RDBC,

CN5,

WORD,

0,

10,

1s

Put_Data,

Output_Data,

0.

WRBC,

CN5,

WORD,

0,

10,

1s

 

 

 

 

 

 

 

 

 

Read function map descriptor gets data from the DeviceNet network and stores it in the Input_Data data array.

Write function map descriptor puts data from the Output_Data data array onto the DeviceNet network.

Note that each address refers to an individual local input and output buffer. Each buffer can contain up to 512 bytes.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 9
Contents Applicability & Effectivity FS-8700-22 X30 DeviceNet Slave Adapter DriverTable of Contents X30 DeviceNet Slave Description RSNetWorx, RSLogix or another Network Scheduling Tool Hardware Connection Tips / Hints Hardware ConnectionsDeviceNet Settings Configuring the FieldServer as a DeviceNet SlaveServer Side Connection Descriptors Server Side Node DescriptorsMacid Driver Specific Map Descriptor Parameters BYTE, WORD, DwordFLOAT, Bool Map Descriptor Example Appendix A.2. Using RSNetWorx Appendix A.3. Using RSLogix FS-8700-22X30DeviceNetSlave Manual This page Intentionally Left Blank