FieldServer FS-8700-16 instruction manual Server Side Connection Descriptions

Page 10

FS-8700-16 BACnet PTP Serial Driver Manual

Page 10 of 20

 

 

5.2.Server Side Connection Descriptions

Section Title

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Port

Port name

 

 

 

P1-P87

 

 

 

 

 

 

 

110;

300;

600;

1200;

Baud*

Specify baud rate

 

 

2400; 4800; 9600; 19200;

 

 

 

 

 

38400; 57600; 115000

Parity*

Specify parity

 

 

Odd, Even, None

 

Data_Bits*

Specify data bits

 

 

7, 8

 

 

 

Stop_Bits*

Specify stop bits

 

 

1,2

 

 

 

Protocol

Specify Protocol Used

 

 

BACnet_PTP

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Connections

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Port,

Baud,

Parity,

Data_Bits,

Stop_Bits,

Protocol

 

P1,

9600,

Even,

7,

1,

 

BACnet_PTP

5.3.Server Side Node Descriptors

Section Title

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

Node_Name8

Provide name for node

Up

to

32

alphanumeric

 

 

 

characters

 

 

Node_ID

BACnet station address of physical Server

1 - 4194303

 

 

 

node

 

 

 

 

 

Protocol

Specify protocol used

BACnet_PTP

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Nodes

 

 

 

 

 

Nodes

 

 

 

 

 

 

Node_Name,

 

Node_ID,

Protocol

 

 

Virtual_BCU_11,

11,

BACnet_PTP

 

 

 

 

 

 

 

 

7Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

8 When using the Trane Tracer Summit Workstation System, this name will appear as the object name

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com

Image 10
Contents FS-8700-16 Bacnet PTP Serial Applicability & EffectivityTable of Contents BACnet Description DescriptionHardware Connections Configuring the FieldServer as a BACnet Client Data Arrays/ DescriptorsClient Side Connection Descriptions AI, AO, AV, BI, BV, MI RDBC, WRBC, WrbxReadproperty Map Descriptor Example Configuring the FieldServer as a BACnet Server Driver Specific FieldServer ParametersServer Side Connection Descriptions FieldServer Specific Map Descriptor Parameters AI, AO, AV, BI, BV, MI, MOServer Side Map Descriptors MapDescriptors Analoginput Appendix B.2. BACnet Priority Arrays Appendix B.4. Network number Appendix B.5 BACnet State Text Preload Trane Specific Tips Appendix C.2 BACnet Specific StatisticsAppendix D. Units Kvar KVAMvar GPM PSIVAR