FieldServer FS-8700-16 instruction manual Server Side Map Descriptors MapDescriptors

Page 12

FS-8700-16 BACnet PTP Serial Driver Manual

Page 12 of 20

 

 

5.4.3.Map Descriptor Example

 

// Server Side Map Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptors_

 

Data_Array_

Data_Array_

Function,

 

Node_Name,

 

 

Data_Type

 

Object_

 

Property,

 

Units,

 

Data_Array_

 

Data_Array_

 

Node_

 

Node_

 

 

Name,

 

Name,

 

Offset,

 

 

 

 

 

Instance,

 

 

 

Low_Scale,

 

High_Scale,

 

Low_Scale,

 

High_Scale

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SMD_AI_01,

 

DA_AI_01,

0,

 

Server,

Virtual_BCU_11,

AI,

1,

 

 

Present_Value,

Deg_F,

0,

 

 

10000,

 

0,

 

 

100

 

 

SMD_AI_02,

 

DA_AI_01,

1,

 

Server,

Virtual_BCU_11,

AI,

2,

 

 

Present_Value,

Deg_F,

0,

 

 

10000,

 

0,

 

 

100

 

 

SMD_AI_03,

 

DA_AI_01,

2,

 

Server,

Virtual_BCU_11,

AI,

3,

 

 

Present_Value,

Deg_F,

0,

 

 

10000,

 

0,

 

 

100

 

 

SMD_AO_01,

 

DA_AO_01,

0,

 

Server,

Virtual_BCU_11,

AO,

1,

 

 

Present_Value,

%RH,

0,

 

 

10000,

 

0,

 

 

100

 

 

SMD_AO_02,

 

DA_AO_01,

1,

 

Server,

Virtual_BCU_11,

AO,

2,

 

 

Present_Value,

%RH,

0,

 

 

10000,

 

0,

 

 

100

 

 

SMD_AO_03,

 

DA_AO_01,

2,

 

Server,

Virtual_BCU_11,

 

AO,

3,

 

 

Present_Value,

%RH,

0,

 

 

10000

 

0,

 

 

100

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

 

 

 

Node_Name,

Data_Type,

 

Object_Instance,

 

Property

 

 

SMD_DI_01,

 

DA_DI_01,

 

0,

 

 

Server,

 

 

 

Virtual_BCU_11,

DI,

 

 

 

1,

 

 

 

 

Present_Value

 

 

SMD_DI_02,

 

DA_DI_01,

 

1,

 

 

Server,

 

 

 

Virtual_BCU_11,

DI,

 

 

 

2,

 

 

 

 

Present_Value

 

 

SMD_DI_03,

 

DA_DI_01,

 

2,

 

 

Server,

 

 

 

Virtual_BCU_11,

DI,

 

 

 

3,

 

 

 

 

Present_Value

 

 

SMD_DO_01,

 

DA_DO_01,

0,

 

 

Server,

 

 

 

Virtual_BCU_11,

DO,

 

 

 

1,

 

 

 

 

Present_Value

 

 

SMD_DO_02,

 

DA_DO_01,

1,

 

 

Server,

 

 

 

Virtual_BCU_11,

DO,

 

 

 

2,

 

 

 

 

Present_Value

 

 

SMD_DO_03,

 

DA_DO_01,

2,

 

 

Server,

 

 

 

Virtual_BCU_11,

DO,

 

 

 

3,

 

 

 

 

Present_Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com

Image 12
Contents FS-8700-16 Bacnet PTP Serial Applicability & EffectivityTable of Contents BACnet Description DescriptionHardware Connections Configuring the FieldServer as a BACnet Client Data Arrays/ DescriptorsClient Side Connection Descriptions RDBC, WRBC, Wrbx AI, AO, AV, BI, BV, MIReadproperty Map Descriptor Example Configuring the FieldServer as a BACnet Server Driver Specific FieldServer ParametersServer Side Connection Descriptions FieldServer Specific Map Descriptor Parameters AI, AO, AV, BI, BV, MI, MOServer Side Map Descriptors MapDescriptors Analoginput Appendix B.2. BACnet Priority Arrays Appendix B.4. Network number Appendix B.5 BACnet State Text Preload Trane Specific Tips Appendix C.2 BACnet Specific StatisticsAppendix D. Units KVA KvarMvar PSI GPMVAR