FieldServer FS-8700-16 Configuring the FieldServer as a BACnet Client, Data Arrays/ Descriptors

Page 5

FS-8700-16 BACnet PTP Serial Driver Manual

Page 5 of 20

 

 

4.Configuring the FieldServer as a BACnet Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Instruction Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet Server.

4.1.Data Arrays/ Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

Section Title

 

 

 

Data_Arrays

 

 

 

Column Title

Function

 

Legal Values

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

characters

 

 

 

 

 

 

Float, Bit, Uint16, Uint32,

Data_Format

Provides data format

 

Sint16, Sint32, Packed_Bit,

 

Byte, Packed_Byte,

 

 

 

 

 

 

Swapped_Byte

Data_Array_Length

Number of Data Objects

1-10,000

 

 

 

 

Example

 

 

 

 

 

 

 

// Data Arrays

 

 

 

Data_Arrays

 

 

 

Data_Array_Name,

Data_Format,

 

Data_Array_Length

DA_AI_01,

Float,

 

200

DA_AO_01,

Float,

 

200

DA_DI_01,

Bit,

 

200

DA_DO_01,

Bit,

 

200

4.2.Setting the FieldServer Node_ID and Network Number

Section Title

 

 

FieldServer

 

 

Column Title

Function

Legal Values

System_Node_ID

Configure Node_ID of FieldServer

1-255

Network_Number

BACnet Network Number

1-65535, 5

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com

Image 5
Contents Applicability & Effectivity FS-8700-16 Bacnet PTP SerialTable of Contents Description BACnet DescriptionHardware Connections Data Arrays/ Descriptors Configuring the FieldServer as a BACnet ClientClient Side Connection Descriptions Readproperty RDBC, WRBC, WrbxAI, AO, AV, BI, BV, MI Map Descriptor Example Driver Specific FieldServer Parameters Configuring the FieldServer as a BACnet ServerServer Side Connection Descriptions AI, AO, AV, BI, BV, MI, MO FieldServer Specific Map Descriptor ParametersServer Side Map Descriptors MapDescriptors Analoginput Appendix B.2. BACnet Priority Arrays Appendix B.4. Network number Appendix B.5 BACnet State Text Preload Appendix C.2 BACnet Specific Statistics Trane Specific TipsAppendix D. Units Mvar KVAKvar VAR PSIGPM