FieldServer FS-8700-112, FCI 7100 Series instruction manual

Page 20

FS-8700-112 FCI 7100 Series Driver Manual

 

 

 

Page 20 of 24

 

 

 

 

 

 

 

 

 

 

 

 

 

Message

 

 

Description

 

 

 

 

 

 

FCI7100:#12a Err. No MD's to store message

 

A message arrived and the driver could

 

 

 

data.

 

 

not find a place to store the data.

 

 

 

FCI7100:#12b Err. No MD's to store message

 

Perhaps you were not expecting this type

 

 

 

data."

 

 

of event/this loop/sensor.

If you are not

 

 

 

FCI7100:#13 Err. Msg was ignored. MD Required

 

interested in the data then ignore the

 

 

 

 

message.

Otherwise

update

the

 

 

 

for Storage.

 

 

configuration file. 3

 

 

 

 

 

FCI7100:#13a Err. Diagnostic 1);

 

Take a log. Try and repeat the event that

 

 

 

FCI7100:#13b Err. Diagnostic 2);

 

caused the message to be printed. Then

 

 

 

FCI7100:#13c Err. Diagnostic 3);

 

contact tech support.

 

 

 

 

 

FCI7100:#14 Err. <%s> file not found., md-

 

 

 

 

 

 

 

 

>mapdesc_name ) ;

 

If this error is repeated often it is possible

 

 

 

FCI7100:#15 Err. Event Type=<%s> Not

 

 

 

 

 

that a FCI firmware update as made the

 

 

 

recognized." , drv_bd->event_desc )

 

driver unusable. Take a log and contact

 

 

 

FCI7100:#16 Err. Point Type='%c'(%#x) Not

 

 

 

 

 

tech support.

 

 

 

 

 

 

recognized. , drv_bd->point_identifier[0] , drv_bd-

 

 

 

 

 

 

 

 

>point_identifier[0] ) ;

 

 

 

 

 

 

 

 

 

 

 

This message should only be printed if a

 

 

 

FCI7100:#17 Err. Loop=%d < 1. Rejected. ,

 

byte in a message has been corrupted. If

 

 

 

drv_bd->loop )

 

 

you notice it more than once then take a

 

 

 

 

 

 

log and contact tech support.

 

 

 

 

FCI7100:#18 Err. Loop Type='%c'(%#x) Not

 

If this error is repeated often it is possible

 

 

 

 

that a FCI firmware update as made the

 

 

 

recognized. , drv_bd->point_identifier[2] , drv_bd-

 

driver unusable. Take a log and contact

 

 

 

>point_identifier[2] )

 

tech support.￿

 

 

 

 

 

 

 

 

 

 

 

 

 

FCI7100:#19 Err. Relay=%d < 1. Rejected. ,

 

This message should only be printed if a

 

 

 

drv_bd->relay

 

 

byte in a message has been corrupted. If

 

 

 

FCI7100:#20 Err. Zone=%d < 1. Rejected. ,

 

you notice it more than once then take a

 

 

 

drv_bd->zone"

 

 

log and contact tech support.

 

 

 

 

FCI7100:#21 Err. Point Type not recognized

 

Valid Point Types are listed in section

 

 

 

FCI7100:#22 Err. Undefined Point Type"

4.4.23

 

 

 

 

 

 

FCI7100:#23 Err. Event Type not recognized

 

Valid Event Types are listed in section

 

 

 

FCI7100:#24 Err. Undefined Event Type

4.4.23

 

 

 

 

 

 

FCI7100:#25a

Err. Address+Length>99. Length

 

The maximum value for a sensor/module

 

 

 

Truncated

 

 

is 99. The combination of address and

 

 

 

FCI7100:#25b

Err. Address+Length>99. Length

 

 

 

 

 

length specified produce a number > 993

 

 

 

Truncated

 

 

 

 

 

 

 

 

 

FCI7100:#26

Err. Invalid Module number.

 

 

 

 

 

 

 

 

Expected 1..99

 

 

 

 

 

 

 

 

 

FCI7100:#27a Err. Invalid Loop number. Expected

 

 

 

 

 

 

 

1..10

 

 

Correct the configuration file3

 

 

 

 

 

 

 

 

 

FCI7100:#27b Err. Invalid Loop number. Expected

 

 

 

 

 

 

 

1..10

 

 

 

 

 

 

 

 

 

FCI7100:#27c Err. Invalid Loop number. Expected

 

 

 

 

 

 

 

1..10

 

 

 

 

 

 

 

3Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to take effect.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 20
Contents FS-8700-112 FCI 7100 Series Serial Driver Table of Contents FS-8700-112 FCI 7100 Series Driver Manual Max Nodes Supported FieldServer Mode CommentsFCI 7100 Series Serial Driver Description Required 3rd Party Configuration Required 3rd Party SoftwareOptional Items FieldServer Technologies DescriptionHardware Connections FCITop right hand side of board Connector J3 label on right Data Arrays/Descriptors Section TitleColumn Title Function Legal Values ExampleClient Side Connection Descriptions Client Side Node Descriptors ‘ResetbyanyNode ‘ thenResetbyanyNode Driver Related Map Descriptor Parameters Page Map Descriptor Example 1 Sensor / Module Events Map Descriptor Example 2 Bit Storage FS-8700-112 FCI 7100 Series Driver Manual FS-8700-112 FCI 7100 Series Driver ManualPage 15 Index Category EventAppendix A.2. Extending the Event Table Appendix A.3. How Data is storedFS-8700-112 FCI 7100 Series Driver Manual Example Appendix A.4. Panel Synchronization Appendix A.6. Networked PanelsMessage Description Appendix B. Driver Error MessagesFS-8700-112 FCI 7100 Series Driver ManualPage 19 Page Page Appendix B.1. Driver Stats Exposed UINT32FCI7100STATNOPLACETOSTORENODE This page Intentionally Left Blank