4.2.Client Side Connection Descriptions
| Section Title |
|
|
|
| Connections |
|
|
|
| Column Title | Function |
| Legal Values |
| Port | Specify which port the device | is | |
|
| connected to the FieldServer |
|
|
| Protocol | Specify protocol used |
| FCI_7100, FCI_7100_series, |
|
| FCI7100 | ||
|
|
|
| |
| Baud* | Specify baud rate |
| 1200 – Vendor Limitation |
| Parity* | Specify parity |
| None – Vendor Limitation. |
| Data_Bits* | Specify data bits |
| 8 – Vendor Limitation |
| Stop_Bits* | Specify stop bits |
| 1 – Vendor Limitation |
| Handshaking* | The 7100 series panels do not support hand | shaking. | |
| Poll _Delay* | This commonly used parameter has no meaning for this driver. |
Example
//Client Side Connections
Connections
Port, | Protocol, | Baud, | Parity |
P8, | FCI_7100, | 1200 | None |
1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.