Page 7 of 16 |
4.2.Client Side Connections
| Section Title |
|
|
| Connections |
|
|
| Column Title | Function | Legal Values |
| Port | Specify which port the device is | |
|
| connected to the FieldServer |
|
| Baud* | Specify baud rate | 300 to 115200; 9600 |
| Parity* | Specify parity | Even, Odd, None |
| Data_Bits* | Specify data bits | 8 |
| Handshaking*4 | Specify hardware handshaking | RTS, RTS/CTS, None |
| Protocol * | Specify protocol used | DF1_FD, DF1_HD_MASTER, |
| DF1_HD_SLAVE | ||
|
|
| |
|
|
|
|
| Example |
|
|
//Client Side Connections
Ports, |
|
|
Port, |
| Protocol |
P8, |
| DF1_FD |
4.3.Client Side Node Descriptors
| Section Title |
|
|
|
|
| Nodes |
|
|
|
|
| Column Title | Function |
| Legal Values |
|
| Node_Name | Provide name for node | Up to 32 alphanumeric characters | ||
| Node_ID | Node ID of physical Server node |
| ||
| (PLC) |
|
| ||
|
|
|
|
| |
| Protocol | Specify protocol used | DF1_FD, DF1_HD_MASTER, | ||
| DF1_HD_SLAVE |
| |||
|
|
|
|
| |
| Port | Specify which port the device is |
| ||
|
| connected to the FieldServer |
|
| |
| PLC_Type | Specify PLC |
| PLC3, PLC5, SLC5 |
|
| Communications type. |
| |||
|
|
|
| ||
| Example |
|
|
|
|
|
|
|
|
|
|
| // Client Side Nodes |
|
|
| |
| Nodes |
|
|
|
|
| Node_Name, | Node_ID, | Protocol, | PLC _Type, | Port |
| PLC_01, | 1, | DF1_FD, | SLC5, | P8 |
3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
4 Handshaking is not supported, only the enabling of the RTS/CTS lines
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)