FieldServer FS-8700-03 DF1 Appendix A.2. Checksum, Appendix A.3. Command Support

Page 14

FS-8700-03 DF1 Driver ManualPage 14 of 16

Appendix A. Driver Notes

Appendix A.1. Continuous Map Descriptors

RS View has been known to crash if it tries to read a Server mapping that is discontinuous.

e.g.

Server map 1:

N21:

0-31

 

Server map 2:

N21:

32-100

This will panic the FieldServer and crash RS view as the DF1 will attempt to map N21: 0-100

If set up as:

Server Map 1: N21: 0-100 No problems are experienced

Appendix A.2. Checksum

You can now specify a checksum parameter for the serial connection. The heading keyword is "Checksum" and the possible values are

1) BCC or 2) CRC-16

If nothing is specified it defaults to BCC.

Example:

Connections

 

 

 

Port,

Baud,

Protocol,

Checksum

P1,

9600,

DF1_FD,

CRC-16

The Checksum is valid for both DF1_FD and DF1_HD.

Appendix A.3. Command Support

The following commands are supported by the FieldServer for the various PLC types:

 

PLC_Type

 

 

File_Type

 

 

FNC

 

 

Read

 

 

FNC

 

 

Write

 

 

Typical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

1

 

 

Range Read

0

 

Range Write

N7: 3, L5

 

PLC3

 

F

1

 

 

Range Read

0

 

Range Write

F12: 3, L5

 

 

 

 

B

1

 

 

Range Read

2

 

Bit Write

 

B3/4: 5, l5

 

 

 

 

N

1

 

 

Range Read

0

 

Range Write

N7: 3 , L5

 

PLC5

 

F

1

 

 

Range Read

67

 

Typed Write

F12: 3, L5

 

 

 

 

B

1

 

 

Range Read

26

 

Read Modify Write

B3/4: 5, L5

 

 

 

 

N

 

A2/A1

 

Protected Typed

 

AA

 

Protected Typed

 

N7: 3, L5

 

 

 

 

 

 

 

 

 

 

Logical Read

 

 

 

 

Logical Write

 

 

 

 

 

 

 

F

 

A2/A1

 

Protected Typed

 

AA

 

Protected Typed

 

B3/4: 5, L7

 

 

 

 

 

 

Logical Read

 

 

Logical Write

 

 

SLC5

 

B

 

A2/A1

 

Protected Typed

 

AB

 

Protected Typed

 

B3/4: 5, L8

 

 

 

 

Logical Read

 

 

Logical Write

 

 

 

 

 

I

 

A2/A1

 

Protected Typed

-

 

-

 

 

I: 13, L5

 

 

 

 

 

 

 

 

 

 

Logical Read

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

A2/A1

 

Protected Typed

-

 

-

 

 

O: 13, L5

 

 

 

 

 

 

Logical Read

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 14
Contents FS-8700-03 DF1 Table of Contents Allen Bradley DF1 Description Provided by the Supplier of 3rd Party Equipment DescriptionHardware Connections Allen Bradley PLCConfiguring the FieldServer as a DF1 Client Data Arrays/DescriptorsClient Side Connections Client Side Node DescriptorsDriver Related Map Descriptor Parameters Map Descriptor Example Configuring the FieldServer as a DF1 Server Server Side Connection DescriptionsServer Side Node Descriptions Driver Specific Map Descriptor Parameters Map Descriptor Example Appendix A.3. Command Support Appendix A.2. ChecksumAppendix B. Error Messages This page Intentionally Left Blank