FieldServer FS-8700-101 instruction manual Appendix C. Driver Error Messages

Page 20

FS-8700-101_Setra Model 370 Digital Pressure Gage ManualPage 20 of 23

Appendix C. Driver Error Messages

Message

 

 

Notes and Corrective Action

Set370:#1 FYI. Use

an

This message is provided for information and may be ignored. Read

Array

called

<%s>

to

Appendix C.1 for more information.

expose diagnostic info.

 

 

 

 

 

 

This message is provided for information and may be ignored. The

Set370:#2a.

FYI.

MD

message is printed when the Map Descriptor length in the

Length=%d assigned by

configuration file has not been specified. The driver makes the

driver.

 

 

 

correction by itself. To stop this message being printed, modify the

 

 

 

 

configuration file to match the length reported in the message.

Set370:#3 Err. No Write

This Driver cannot be used to write to the Setra device. Remove

MD's allowed.

 

any Map Descriptors whose function requires the FieldServer to

 

write to the Setra device. 3

Set370:#4

FYI.

MD

This message is provided for information and may be ignored. The

address parameter is ignored by the driver. To stop this message

param=Address has

no

being printed, remove the address parameter from the configuration

meaning. Ignoring.

 

file.

 

 

 

 

 

 

 

 

 

 

There are a few variations of this message. Note the variation and

Set370:#5

 

Err.

report the error to FieldServer tech support. You cannot resolve this

Diagnostic x

 

 

error yourself. The error is printed when the driver executes a

 

 

 

 

diagnostic function used for QA testing.

Set370:#6 Err. Array too

The Data Array associated with the reported MD is too short to store

short. DA=%s MD=%s

all the data returned by the Setra Gage. Increase the length of the

Data Array and of the Map Descriptor.3

 

 

 

 

The response to a pressure reading request cannot be parsed by the

Set370:#7 Err. Pressure

driver.

Use the connection view to check the number of protocol

message

can’t

be

errors.

If they keep rising, then take a log and report the error to

parsed. Abandoned!

 

FieldServer Tech Support. If the protocol errors are occasional then

 

 

 

 

ignore them.4

 

 

 

 

The response to a status reading request cannot be parsed by the

Set370:#8* Err. Status

driver.

Use the connection view to check the number of protocol

message

can’t

be

errors. If they keep rising, then take a log and report the error to

parsed. Abandoned!

 

FieldServer Tech Support. If the protocol errors are occasional then

 

 

 

 

ignore them.

 

 

 

 

A Map Descriptor is found which does not have the ‘Gage_Function”

Set370:#9 FYI. Default

specified. The driver assumes your intention was to read the Gage’s

to reading pressure.

 

pressure. If you wish stop this message being printed then modify

 

 

 

 

the configuration file and specify the ‘Gage_Function’ = ‘Pressure’.3

Set370:#10 Err. DA=%s

This message is printed when the driver is configured as a Server.

The Data Array associated with the reported MD is too short to store

too

short.

Act=%d

the message. Modify the MD length and the DA length and try

Rqd=%d MD=%s

 

again.3

 

3 Modify the configuration CSV file. Download the modified file to the FieldServer and reset the FieldServer for the changes to take effect.

4Message is printed once and then suppressed. This is to prevent the error log filling with redundant repetition and thus obscuring other important information.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 20
Contents FS-8700-101 Setra Digital Pressure Gage Model Table of Contents Comments Mode Setra Model 370 Digital Pressure Gage DescriptionFS-8700-101Setra Model 370 Digital Pressure Gage Manual Max Nodes Supported FieldServerFS-8700-101 Driver Manual Required 3rd Party ConfigurationFieldServer Technologies Description FS-8917-01 Hardware Connections O O O O O O O O O O Hardware Connection Tips / HintsO O O O O O O O O O O Data Arrays/Descriptors Section TitleColumn Title Function Legal Values ExampleClient Side Connection Descriptors Client Side Node DescriptorsDriver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example #1 Read Pressure Dapressure RdbcMap Descriptor Example #2 Read Status Dastatus RdbcMap Descriptor Example #3 Verify Daverify RdbcServer Side Connection Descriptors Server Side Node Descriptors Driver Specific Map Descriptor Parameters Server Map Descriptor Example DapressureOffset where x is the offset Specified in the MD Appendix A.1.2. Status DataCommand Code Appendix A.2. Gage Pressure UnitsAppendix A.3. Driver Limitations & Exclusions Index # MeaningFS-8700-101Setra Model 370 Digital Pressure Gage Manual Appendix C. Driver Error Messages MessageAppendix C.1. Exposing Driver Diagnostic Statistics Data Array Offset ContentsAppendix C.2. Standard Driver Stats Driver Statistics Recorded ExplanationThis page Intentionally Left Blank