2.Driver Scope of Supply
2.1.Supplied by FieldServer Technologies for this driver
FieldServer Technologies | Description | |
PART # | ||
| ||
| Connector, 25 pin male: Connects to DCE, RTS/CTS loop | |
| Driver Manual. |
2.2.Provided by the Supplier of 3rd Party Equipment
2.2.1.Required 3rd Party Hardware
Part #
M370
Description
SETRA DIGITAL PRESSURE GAGE
2.2.2.Required 3rd Party Configuration
The M370 Gage must be configured using the operator’s manual and the front panel push buttons so that its serial port settings match the FieldServer settings.
The following notes have been extracted from the operator’s manual.
The Setra Digital Pressure Gage is capable of interfacing with a wide variety of computers or other devices through the
1.Press CONV until the gage is displaying pressure units (make sure it is not displaying in "ft" or "meters").
2.Press the
3.Enter "5555". This is the baud rate access code.
4.Press SETUP. The display will read "CAL br".
5.Enter the baud rate. Choose either 300, 600, 1200, 1800, 2400, 3600, 4800or 9600.
6.Press SETUP.
The baud rate is factory set to 2400. If you change the baud rate and wish the gage to retain the new rate after power is removed and restored, repeat steps