FieldServer FS-8700-101 Client Side Connection Descriptors, Client Side Node Descriptors

Page 8

FS-8700-101_Setra Model 370 Digital Pressure Gage Manual

Page 8 of 23

4.2.Client Side Connection Descriptors

 

Section Title

 

 

 

Connections

 

 

 

Column Title

Function

Legal Values

 

Port

Specify which port the device is

P1-P8, R1-R21

 

 

connected to the FieldServer

 

 

Protocol

Specify protocol used

Setra370

 

Baud*

Specify baud rate

110 – 115200, standard baud

 

rates only, 2400.

 

 

 

 

Parity*

Specify parity

Even, Odd, None, Mark, Space

 

Data_Bits*

Specify data bits

7, 8

 

Stop_Bits*

Specify stop bits

1

 

 

Specify hardware handshaking

 

 

Handshaking*

The Setra Model 370 does not support

RTS, RTS/CTS, None

 

 

handshaking.

 

 

Poll _Delay*

Time between internal polls

0-32000 seconds, 1 second

Example

//Client Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

Setra370,

2400,

None,

None,

0.100s

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

Nodes

 

 

 

Column Title

Function

Legal Values

 

Node_Name

Provide name for node

Up to 32 alphanumeric

 

characters

 

 

 

 

Node_ID

This commonly used parameter has no meaning for this driver and may be

 

omitted.

 

 

 

 

 

Protocol

Specify protocol used

Setra370.

 

Connection

Specify which port the device is connected

P1-P8, R1-R21

 

 

to the FieldServer

 

 

Example

 

 

//Client Side Nodes

Nodes

 

 

Node_Name,

Protocol,

Connection

Gage1,

Setra370,

P8

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Image 8
Contents FS-8700-101 Setra Digital Pressure Gage Model Table of Contents Comments Mode Setra Model 370 Digital Pressure Gage DescriptionFS-8700-101Setra Model 370 Digital Pressure Gage Manual Max Nodes Supported FieldServerFS-8700-101 Driver Manual Required 3rd Party ConfigurationFieldServer Technologies Description FS-8917-01 Hardware Connections O O O O O O O O O O Hardware Connection Tips / HintsO O O O O O O O O O O Data Arrays/Descriptors Section TitleColumn Title Function Legal Values ExampleClient Side Connection Descriptors Client Side Node DescriptorsDriver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example #1 Read Pressure Dapressure RdbcMap Descriptor Example #2 Read Status Dastatus RdbcMap Descriptor Example #3 Verify Daverify RdbcServer Side Connection Descriptors Server Side Node Descriptors Driver Specific Map Descriptor Parameters Server Map Descriptor Example DapressureOffset where x is the offset Specified in the MD Appendix A.1.2. Status DataCommand Code Appendix A.2. Gage Pressure UnitsAppendix A.3. Driver Limitations & Exclusions Index # MeaningFS-8700-101Setra Model 370 Digital Pressure Gage Manual Appendix C. Driver Error Messages MessageAppendix C.1. Exposing Driver Diagnostic Statistics Data Array Offset ContentsAppendix C.2. Standard Driver Stats Driver Statistics Recorded ExplanationThis page Intentionally Left Blank