| Page 8 of 23 |
4.2.Client Side Connection Descriptors
| Section Title |
|
|
| Connections |
|
|
| Column Title | Function | Legal Values |
| Port | Specify which port the device is | |
|
| connected to the FieldServer |
|
| Protocol | Specify protocol used | Setra370 |
| Baud* | Specify baud rate | 110 – 115200, standard baud |
| rates only, 2400. | ||
|
|
| |
| Parity* | Specify parity | Even, Odd, None, Mark, Space |
| Data_Bits* | Specify data bits | 7, 8 |
| Stop_Bits* | Specify stop bits | 1 |
|
| Specify hardware handshaking |
|
| Handshaking* | The Setra Model 370 does not support | RTS, RTS/CTS, None |
|
| handshaking. |
|
| Poll _Delay* | Time between internal polls |
Example
//Client Side Connections
Connections
Port, | Protocol, | Baud, | Parity, | Handshaking, | Poll_Delay |
P8, | Setra370, | 2400, | None, | None, | 0.100s |
4.3.Client Side Node Descriptors
| Section Title |
|
|
| Nodes |
|
|
| Column Title | Function | Legal Values |
| Node_Name | Provide name for node | Up to 32 alphanumeric |
| characters | ||
|
|
| |
| Node_ID | This commonly used parameter has no meaning for this driver and may be | |
| omitted. |
| |
|
|
| |
| Protocol | Specify protocol used | Setra370. |
| Connection | Specify which port the device is connected | |
|
| to the FieldServer |
|
| Example |
|
|
//Client Side Nodes
Nodes |
|
|
Node_Name, | Protocol, | Connection |
Gage1, | Setra370, | P8 |
1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408)