Minuteman UPS E700RM1U, E1500RM1U Replacing the Battery, Qualified Service Personnel only

Page 17

English

REPLACING THE BATTERY

(QUALIFIED SERVICE PERSONNEL ONLY)

The Enterprise 1U Rackmount Series UPS has an easy to replace hot-swappable batteries. Please read all of the WARNINGS and CAUTIONS before attempt- ing to service the batteries.

NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up.

WARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONLY.

CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.

CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly. Refer

to local codes for proper disposal requirements or return the battery to MINUTEMAN.

CAUTION: Although battery system voltages are only 24VDC the battery system can still present a risk of electrical shock. These batter- ies produce sufficient current to burn wire or tools very rapidly,

producing molten metal. Observe these precautions when re- placing the batteries:

1.Remove watches, rings, or other metal objects.

2.Use hand tools with insulated handles.

3.Wear protective eye gear (goggles), rubber gloves and boots.

4.Do not lay tools or other metal parts on top of batteries.

5.Disconnect the charging source prior to connecting or disconnecting the battery terminals.

6.Determine if the battery is inadvertently grounded. If the bat- tery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock.

The likelihood of such shock will be reduced, if such grounds are removed during installation and maintenance.

16

Image 17
Contents Enterprise 1U Rackmount Series English Important Safety Instructions English Receiving Inspection Para Systems Life Support Policy Control Panel English Rear Panel Installation PlacementConnecting the Batteries InstallationInstalling the UPS in a 4-post rack Connecting Your Equipment System Overview Turning the Unit ON/OFFSelf Test AlarmsOverload Symptom Possible Cause What To Do Qualified Service Personnel only Replacing the BatteryBattery Replacement Procedure English If the UPS Requires Service System Specifications Battery System EPO English Limited Product Warranty Declaration of Conformity Robert CalhounEnglish PN 34000256 Rev.1