English
(These items may require optional software or hardware)
Function | Factory | User Choices | Description |
| Default |
|
|
UPS ID | Enterprise 1U | Up to 64 | Use this function to uniquely |
| RM Series | characters | identify the UPS in your network |
|
| to define | configuration |
|
| the UPS |
|
Battery | Date of | Date of battery | Enter the current date when |
install | manufacture | replacement - | replacing batteries |
date |
| month/day/year |
|
|
| XX/XX/XXXX |
|
Battery | 1826 | Up to 5 | At first battery replacement, reset |
life in |
| characters | to reflect actual number of days |
days |
|
| |
|
| experience in your environment or | |
|
|
| |
|
|
| leave factory default |
|
|
|
|
Enable/ | Enabled | Enable | When enabled, the UPS will |
Disable |
| or | automatically restart from a low |
auto |
| Disable | battery shutdown when normal AC |
restart |
|
| returns |
Set | Enabled | Enabled, at | Enabled - the UPS will emit a |
audible |
| low battery, | short beep when in the battery |
alarm |
| disabled | mode. At Low Battery the UPS |
state |
|
| will emit two beeps from low |
|
|
| battery warning until shutdown. |
|
|
| Disabled - Use only when software |
|
|
| is controlling the UPS or to |
|
|
| silence the alarm |
|
|
|
|
Shut- | Entire UPS | Entire UPS or | Entire UPS - Turns off the entire |
down |
| UPS output | UPS. |
Type |
|
| UPS Output - Turns off the UPS's |
|
|
| output receptacles only. |
|
|
|
|
Set | 120VAC | 120, 127VAC | Changes output voltage for bat- |
inverter |
|
| tery mode operation |
output |
|
|
|
voltage |
|
|
|
|
|
|
|
Enable/ | Disabled | Enable | Enabled - the UPS will be |
Disable |
| or | completely powered off and re- |
EPO |
| Disable | main off until the UPS is reset |
|
|
|
|
22