Minuteman UPS E1500RM1U, E1000RM1U, E700RM1U user manual System Specifications

Page 21

English

SYSTEM SPECIFICATIONS

 

Model Number

E700RM1U

 

E1000RM1U

E1500RM1U

 

 

 

 

 

 

 

Topology

 

Line-Interactive, Sine Wave

 

 

 

 

 

 

 

Maximum Power Capacity

700VA

 

1000VA

1500VA

 

490W

 

700W

900W

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

Number of Phase

 

 

Single (12W +G)

 

 

Nominal Voltage

 

 

120VAC

 

 

 

 

 

 

 

 

Acceptable Input voltage

 

 

0 - 165VAC

 

 

 

 

 

 

 

 

Voltage Range

 

 

85 - 150VAC

 

 

 

 

 

 

 

Frequency Limits

50 or 60 Hz, +/-6Hz, autosensing

 

 

 

 

 

 

Low Voltage Transfer Point

85V resets to Utility Power at 90V or higher

 

 

 

 

 

 

High Voltage Transfer Point

150V resets to Utility Power at 145V or lower

 

 

 

 

 

 

Input Protection

 

Resettable Circuit Breaker

 

 

 

 

 

OUTPUT NON-BATTERY OPERATION

 

 

Voltage Range

120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)

 

 

 

 

 

 

Voltage Regulation

120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)

 

Frequency Range

60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz

 

 

 

 

 

 

 

Efficiency (Line Mode)

 

 

>93% (Full Load)

 

 

 

 

 

 

OUTPUT BATTERY OPERATION

 

 

 

 

 

 

 

 

Waveform Type

 

 

Sine Wave

 

 

 

 

 

 

 

Nominal Voltage

Default 120VAC User selectable 120/127VAC

 

 

 

 

 

Voltage Regulation

Nominal +/-2% (until Low Battery Warning)

 

 

 

 

 

Frequency

50/60Hz, +/-0.1Hz (unless synchronized to utility)

 

 

 

 

 

Voltage T.H.D.

<5% (Linear Load)

<8% (Linear Load)

 

 

 

 

 

Dynamic Response

+/-5% @ 100% Load change in 100mS

 

 

 

 

 

 

 

Transfer Time

 

 

2-6 mS Typical

 

 

 

 

 

 

 

 

Slew Rate

 

 

<1Hz/Second

 

 

 

 

 

 

 

Overload Capacity

 

110% for 20-Seconds

 

 

 

125% for 10-Seconds

 

 

 

 

150% Shutdown Immediately

 

 

 

 

 

Protection

Over-Current, Short-Circuit Protected and Latching Shutdown

 

 

 

 

 

 

20

Image 21
Contents Enterprise 1U Rackmount Series English Important Safety Instructions English Receiving Inspection Para Systems Life Support Policy Control Panel English Rear Panel Installation PlacementConnecting the Batteries InstallationInstalling the UPS in a 4-post rack Connecting Your Equipment System Overview Turning the Unit ON/OFFSelf Test AlarmsOverload Symptom Possible Cause What To Do Qualified Service Personnel only Replacing the BatteryBattery Replacement Procedure English If the UPS Requires Service System Specifications Battery System EPO English Limited Product Warranty Declaration of Conformity Robert CalhounEnglish PN 34000256 Rev.1