Performance Data
Model LET/LLE Electric Defrost 60 Hz
|
| Capacity |
| Fan Data |
| ||
| Model | 10°F TD | 6°C TD |
|
|
|
|
| No. | CFM | m3H | ||||
|
| ||||||
|
| BTUH | Watts |
|
|
|
|
| LET035 | 3,500 | 1,025 | 1 | 700 |
| 1,189 |
| LET040 | 4,000 | 1,170 | 1 | 700 |
| 1,189 |
| LET047 | 4,700 | 1,380 | 1 | 650 |
| 1,104 |
| LET065 | 6,500 | 1,900 | 2 | 1,400 |
| 2,379 |
Inch | LET075 | 7,500 | 2,200 | 2 | 1,300 |
| 2,209 |
LET090 | 9,000 | 2,640 | 2 | 1,300 |
| 2,209 | |
Per |
| ||||||
LET120 | 12,000 | 3,520 | 3 | 2,100 |
| 3,568 | |
6 Fins |
|
|
|
|
|
|
|
LET140 | 14,000 | 4,100 | 3 | 1,950 |
| 3,313 | |
LET160 | 16,000 | 4,690 | 4 | 2,600 |
| 4,418 | |
| LET180 | 18,000 | 5,280 | 4 | 2,600 |
| 4,418 |
| LET200 | 20,000 | 5,860 | 5 | 3,250 |
| 5,522 |
| LET240 | 24,000 | 7,030 | 6 | 3,900 |
| 6,627 |
| LET280 | 28,000 | 8,200 | 6 | 3,900 |
| 6,627 |
| LLE041 | 4,100 | 1,200 | 1 | 690 |
| 1,172 |
Inch | LLE068 | 6,800 | 2,000 | 2 | 1,380 |
| 2,345 |
LLE080 | 8,000 | 2,340 | 2 | 1,380 |
| 2,345 | |
|
| ||||||
Per | LLE102 | 10,200 | 2,990 | 3 | 2,170 |
| 3,687 |
LLE136 | 13,600 | 3,990 | 4 | 2,760 |
| 4,690 | |
Fins |
| ||||||
LLE170 | 17,000 | 4,980 | 5 | 3,450 |
| 5,862 | |
4 |
|
|
|
|
|
|
|
LLE204 | 20,400 | 5,980 | 6 | 4,140 |
| 7,035 | |
|
| ||||||
| LLE235 | 23,500 | 6,880 | 6 | 4,140 |
| 7,035 |
Model LET/LLE Electric Defrost 50 Hz †
|
| Capacity |
| Fan Data |
| ||
| Model | 10°F TD | 6°C TD |
|
|
|
|
| No. | CFM | m3H | ||||
|
| ||||||
|
| BTUH | Watts |
|
|
|
|
| LET035 | 3,325 | 974 | 1 | 630 |
| 1,070 |
| LET040 | 3,800 | 1,113 | 1 | 630 |
| 1,070 |
| LET047 | 4,465 | 1,308 | 1 | 586 |
| 995 |
| LET065 | 6,175 | 1,809 | 2 | 1,260 |
| 2,142 |
Inch | LET075 | 7,125 | 2,087 | 2 | 1,170 |
| 1,989 |
LET090 | 8,550 | 2,504 | 2 | 1,170 |
| 1,989 | |
Per |
| ||||||
LET120 | 11,400 | 3,339 | 3 | 1,891 |
| 3,213 | |
6 Fins |
|
|
|
|
|
|
|
LET140 | 13,300 | 3,896 | 3 | 1,756 |
| 2,984 | |
LET160 | 15,200 | 4,452 | 4 | 2,341 |
| 3,978 | |
| LET180 | 17,100 | 5,009 | 4 | 2,341 |
| 3,978 |
| LET200 | 19,000 | 5,565 | 5 | 2,927 |
| 4,973 |
| LET240 | 22,800 | 6,678 | 6 | 3,512 |
| 5,967 |
| LET280 | 26,600 | 7,791 | 6 | 3,512 |
| 5,967 |
| LLE041 | 3,895 | 1,141 | 1 | 621 |
| 1,056 |
Inch | LLE068 | 6,460 | 1,892 | 2 | 1,243 |
| 2,111 |
LLE080 | 7,600 | 2,226 | 2 | 1,243 |
| 2,111 | |
|
| ||||||
Per | LLE102 | 9,690 | 2,838 | 3 | 1,954 |
| 3,320 |
LLE136 | 12,920 | 3,784 | 4 | 2,485 |
| 4,223 | |
Fins |
| ||||||
LLE170 | 16,150 | 4,731 | 5 | 3,107 |
| 5,279 | |
4 |
|
|
|
|
|
|
|
LLE204 | 19,380 | 5,677 | 6 | 3,728 |
| 6,334 | |
|
| ||||||
| LLE235 | 22,325 | 6,539 | 6 | 3,728 |
| 6,334 |
Capacity Correction Factors For Electric and Hot Gas Defrost Units
Saturated Suction | +20 | ||||
Temperature °F |
|
|
|
| |
Saturated Suction | |||||
Temperature °C | |||||
|
|
|
| ||
Multiply Capacity | 1.15 | 1.04 | 1.00 | 0.90 | |
By | |||||
|
|
|
|
†For EC motors, use 60 Hz capacity and airflow values (Units with EC motors operating at 50 Hz will not see a reduction in performance due to the electronic control of the motor)