Hot Gas Reverse Cycle Kits
HGT 6 FPI
|
|
|
| ||
TXV Bypass Assembly Kits | TXV Bypass Assembly Kits | ||||
SQE/SBF | EG | HFESC | SQE/SBF | EG | HFESC |
50169210
50169211
50169212
50169213
50169214
50169215
50169216
50169217
50169218
52733701
52733702
52733703
52733704
52733705
52733706
52733707
52733708
52733709
HGT 4 FPI
235
50169210
50169211
50169212
50169213
50169214
50169215
50169216
50169217
50169218
52733701
52733702
52733703
52733704
52733705
52733706
52733707
52733708
52733709
Drain Pan Loop | Suction Line | Drain Pan Loop | Suction Line |
Check Valve Kit | Check Valve Kit | Check Valve Kit | Check Valve Kit |
HGT 6 FPI
50169304
50169305
50169306
50169604
50169605
50169606
52733601
52733602
52733603
52733801
52733802
52733803
HGT 4 FPI
041
50169304
50169305
50169306
50169604
50169605
50169606
52733601
52733602
52733603
52733801
52733802
52733803
Recommendation is that both check valve kits are ordered: (For hot gas models with the hot gas loop drain pan ONLY)
NOTE: The drain pan check valve kit can be ordered as an independent item. But the suction line check valve kit must be ordered with the drain pan check valve kit in order to complete the piping.
NOTE: When using the hot gas units with a hot gas loop drain pan on 0°F applications and below, an insulated drain pan is required.
The hot gas unit coolers can be used in reverse cycle hot gas defrost systems using multiple evaporators connected to one condensing unit. Generally, not more than
During the reverse cycle defrost, the reversing valve; located in the compressor discharge line, diverts hot gas through the suction line to the evaporator. See piping view in Figure 1. The suction line check valve directs the hot gas through the drain pan loop which prevents condensate in the pan from freezing. The hot gas exits the loop at the pan loop outlet header and enters the evaporator through the check valve assembly. As the hot gas defrosts the coil, heat is removed from the hot gas and eventually it condenses into a liquid and exits the coil at the distributor sideport. The liquid then flows through the check valve of the thermostatic expansion valve bypass assembly, around the thermostatic expansion valve, and into the system liquid line. The liquid refrigerant then feeds other evaporators on the cooling cycle, evaporates, and returns to the compressor through their suction lines.
13