Heatcraft Refrigeration Products BN-LOPTB manual PipeHot Gas Defrost, For hot gas models with the

Models: BN-LOPTB

1 20
Download 20 pages 14.49 Kb
Page 15
Image 15
3-Pipe Hot Gas Defrost

3-Pipe Hot Gas Defrost

The hot gas defrost unit coolers conforms to the standard 3-pipe hot gas system using a check

valve assembly, an electrical control to terminate the defrost, and a hot gas solenoid valve. The

check valve assembly transports the hot gas between the drain pan loop and the sideport distributor of the coil. The check valve assembly kit

is available for shipped-loose or factory-installed for an additional cost.

The electrical control option includes an adjustable defrost termination and fan delay control (DTFD) which is standard. An optional

(2) control electrical system is available with one adjustable control for defrost termination (DT)

and one fixed control for the fan delay (FD) for an additional cost. For both the DTFD and DT adjustable controls, the remote bulb position is

with the bulb strapped to the suction line to insure a complete defrost. The remote bulb is positioned

by the installer. The hot gas solenoid valve must be

ordered separately and will be shipped-loose. The thermostatic expansion valve could be ordered separately and shipped- loose or the thermostatic expansion valve could be factory-installed with a liquid line for an additional cost.

The liquid line is designed for the body styles of the Sporlan SQE, SBF, EG and the Alco HFESC thermostatic expansion valves. The thermostatic expansion valve needs to be selected by the sales engineer. In a typical 3-pipe, multiple evaporator system, the compressor discharge defrosts the evaporator. The liquid/vapor mixture of refrigerant after defrost, however, returns to the common suction line of the system. In order to provide sufficient re-evaporation of the liquid vapor mixture and sufficient heat for defrost, no more than one-third of the system should be defrosted at one time. Some means of control in the 3-pipe hot gas system should be supplied to regulate the large amount of liquid returning to the compressor, refrigerant slugging can otherwise damage the compressor.

HGT 6 FPI

 

Shipped-loose

 

 

Factory-installed

 

 

TXV Liquid Line

 

 

TXV Liquid Line

 

SQE/SBF

EG

HFESC

SQE/SBF

EG

HFESC

035-075

090-160

180-280

50169410

50169411

50169412

50169413

50169414

50169415

50169416

50169417

50169418

52733901

52733902

52733903

52733904

52733905

52733906

52733907

52733908

52733909

HGT 4 FPI

041-080

102-204

235

50169410

50169411

50169412

50169413

50169414

50169415

50169416

50169417

50169418

52733901

52733902

52733903

52733904

52733905

52733906

52733907

52733908

52733909

For hot gas models with the

Shipped-loose

Factory-installed

hot gas loop drain pan only

Drain Pan Loop Check Valve Kit

Drain Pan Loop Check Valve Kit

 

 

When using the hot

HGT 6 FPI

 

 

gas units with a hot

 

 

035-075

50169504

52739601

gas loop drain pan on

0°F applications and

090-160

50169505

52739602

below, an insulated

180-280

50169506

52739603

drain pan is required.

HGT 4 FPI

 

 

 

 

 

 

041-080

50169504

52739601

 

102-204

50169505

52739602

 

235

50169506

52739603

15

Page 15
Image 15
Heatcraft Refrigeration Products BN-LOPTB PipeHot Gas Defrost, For hot gas models with the, hot gas loop drain pan only