| Frequency | 50 or 60 Hz |
|
|
| (on battery) |
|
|
|
| Transfer Time | 2/4 milliseconds, including detection time | ||
PROTECTION | Spike Protection | 320 joules, 2ms |
|
|
and FILTERING | Overload Protection | UPS automatic shutdown if overload exceeds 110%of | ||
|
| nominal at 60 seconds and 130% at 3 seconds. | ||
| Unit Input | Fuse for overload & short circuit protection | ||
| Short Circuit | UPS output cut off immediately or input fuse protection | ||
BATTERY | Type | Sealed, |
| |
| Typical Recharge Time | 4 hours ( to 90% of full capacity) |
| |
| Back up Time | |||
PHYSICAL | Net Weight kg (lbs) | 5.0 (11) | 5.5 (12) | 6.0 (13) |
| Shipping Weight kg | 5.5 (12) | 6.0 (13) | 6.5 (14) |
| (lbs) |
|
|
|
| Dimension (mm) | 97 x 260 x 135 |
|
|
| WxDxH |
|
|
|
| Input Inlet | IEC 320 power inlet |
| |
INDICATOR | Line normal | Steady ON of green LED |
| |
| Battery in use | Slow blinking of green LED (about 0.47Hz) | ||
| Battery low | Fast blinking of green LED (about 1.825 Hz) | ||
| Over low | Very rapid blinking of green LED (about 3.75 Hz) | ||
|
| between 110% to 130% load. |
| |
ALARM | Battery in use | Slow beeping sound (about 0.74 Hz ) 1 minute | ||
| Battery low | Medium beeping sound (about 1.825Hz) | ||
| Over load | Rapid beeping sound (about 3.75 Hz) within 110% | ||
|
| to130% load. |
|
|
CONFORMANCE | Safety | cUL, TUV, CE, meet FCC |
| |
| Surge | Meet IEEE 587 standard |
| |
ENVIRONMENT | Ambient operation | 3,500 meters max. elevation, | ||
|
| condensing |
| |
| Audible noise | <40 dBA (1 meter from surface ) |
| |
| Storage condition | 15000 meters max. elevation |
|