The relay cards are directly related to any alarms that occur on the Hawk 3. The single relay is a “Form C” relay that activates in relationship to “SP1”. The dual relay is a Form C” relay that activates in relationship to “SP1” & “SP2”.

The quad relay is a “Form A” relay that activates in relationship to “SP1” through “SP4”.

NOTE: “SP3” and “SP4” connections share a common.

!

All relay contacts are rated at 250VAC @ 5 amp maximum. The rating of the relay contact is intended for resistive circuits only. Use a snubber circuit to protect the contacts from inductive loads.

7.2Frequently Asked Questions

What is a Form A or Form C relay?

The form A relay is a 1 contact switch that is either closed or open. The form C relay has 2 contacts, one of which will be closed and one open. With the fac- tory defaults used, N.O. on the relay means normally open when the Hawk 3 is not in alarm. N.C. means normally closed when the Hawk 3 is not in alarm.

What does N.D. and N.E. do to the relay?

The effect of the relay can be reversed by setting the relay action to N.E. (nor- mally energized) in the menu. When the Hawk 3 is not in alarm, the N.C. contact will now be open and the N.O contact will be closed. Setting the alarm response back to N.D. (normally de-energized) will put the contacts back to their default state.

7.3Power Supply Card

Universal AC Supply 3-1/2 Digit 120 VAC Supply DC to DC Supply

6.4

Output Control (If Present)

 

 

 

 

 

 

 

 

 

 

OctL

 

 

 

 

 

ALog out

 

 

 

 

 

 

LIM

HI (electrical limit)

 

 

 

 

 

(100*)

 

 

 

 

 

Lo (electrical limit)

 

 

 

 

 

(0*)

 

 

 

 

FS (Fail safe)

HI (move to 20mA)

 

 

 

 

(Overrange or Underrange

LO (move to 4mA)

 

 

 

 

 

Off*

 

6.5System Control

(The process meter will have pre-loaded coordinates)

SctL

 

FACT/rSET (Factory

Reset (Selecting this item will reset the

 

Reset)

device to default values and return to

 

 

menu)

IN ~

IN

~

IN ~

IN

~

85-250VAC

85 - 250 VAC

50/60 Hz

50/60 Hz

10VA

10VA

HOLD

HOLD

+

9-36VDC

10W

HOLD

The AC power cards are meant to operate from standard 50/60 Hz line power. The DC to DC power card is an isolated supply that can operate between 9 and 32 volts DC.

14

11

Image 11
Contents Simpson Electric Company 520 Simpson Avenue Operators ManualTechnical Assistance Warranty and ReturnsPage Contents General Description SpecificationsIntroduction Output ControlMounting Requirements Installation and Panel CutoutDisplay and Keypad Controls Display ControlRelay Control Sp1-Sp4 Engineering Label PlacementMenu Detail Operating the Keys Run ModeProgram Mode Edit ModeRelay Control Menu Flowchart Programming MenuMeasurement Control System Control Frequently Asked QuestionsPower Supply Card Output Control If PresentSingle Relay Dual Relay Quad Relay Temperature Input CardsPassword Relay Cards