Nortel Networks 8010 manual Operational Notes for the Power Supply

Page 11

8964FA

5.Turn on the power switch.

Note: In a newly installed chassis that requires two power supplies (nonredundant configuration), you must turn on both units within 2 seconds of each other. If you wait longer to turn on the second power supply, both power supplies will turn off. To correct this condition, turn off both power supplies, wait at least 30 seconds, and turn both power supplies on again within 2 seconds.

Operational Notes for the Power Supply

A Passport 8010 Chassis with up to five installed modules can operate with one installed power supply. For a redundant power configuration, install two power supplies.

A Passport 8010 Chassis with more than five installed modules requires a minimum of two power supplies for a nonredundant configuration. A redundant configuration for such a chassis requires three power supplies.

In a chassis with a nonredundant power supply configuration, if one power supply fails, the system loses power and network connectivity.

In a chassis with two installed power supplies, you can add a third power supply without powering down the chassis.

When you first install a Passport 8000 Series chassis that requires two power supplies (nonredundant configuration), you must turn on both power supply units within 2 seconds of each other. If you wait longer to turn on the second power supply, both power supplies will turn off. To correct this condition, turn off both power supplies, wait at least 30 seconds, and turn both power supplies on again within 2 seconds.

7

Image 11
Contents Installing the Passport 8010 Chassis USA Requirements Only Japan/Nippon Requirements Only Page About this Guide Before You Begin Unpacking Attaching the Rack-Mounting Brackets Installing the Chassis in a Rack Installing the Power Supply Operational Notes for the Power Supply Attaching a Cable Guide Installing a Module Environmental Specifications Chassis SpecificationsSafety Agency Approvals