Atlantis Land 3001 Power, Input, Output, Transfer, Battery, Protection, Connections, LED Display

Page 2

HostPower3001

Line Interactive UPS

Server UPS S3000. Potenza 3000 VA (1800W). Tecnologia Line Interactive ad onda sinusoidale con stabilizzazione di tensione. Filtri di protezione di linea telefonica o LAN . Batterie tipo “long-life”. Autonomia 15 minuti al 50% del carico . Batterie “HotSwap” sostituibili dall’utente. Display LCD con stati di fun- zionalità e parametri elettrici. Software di shutdown automatico e diagnostica del server per Windows 95/98/2000 Linux e UNIX..

Specifiche Tecniche

Power

3000VA / 1800W

Input

Voltage Single Phase; 220/230/240V selectable by DIP Switch (±25% )

HZ 50Hz/60Hz ±5%

Output

Voltage(AC) Increase 15% (Input:-9% to

-25%); Decrease 15% (Input:+9% to +25%)

Voltage(INV) Inverter mode:±3%

Waveform(INV) Pure Sine-Wave with THD 3% at linear load

Hz(INV) Inverter mode: 50Hz or 60Hz ± 0.1Hz

Transfer

Line/Battery Nearly Zero Transfer (<6ms typi-

cal)

Battery

Half-load runtime 9 min

Capacity 12V/9Ah

Quantity 4

Recharge Time 2-4 Hours to 90%

Type Sealed Maintenance Free Lead Acid VRLA

Type

Protection

Over/under Volt. Switch to Battery Output whrn the Utility over regulation range

Overload(AC/INV) >110% Buzzer continuosly alarms and shuts down after 10 minutes

Short Circuit(AC/INV) Input Fuse & Electronic Circuit / Electronic Circuit

Low Battery Two stages, no battery drain after cut-off

EMI/RFI Full time suppression

Surge Protection Meet with IEEE 587 cat. A&B Standard

Modem/Network RJ11 / RJ45

Energy Rating 960 Joules instantaneous response

Attenuation Better than 45dB @1Mhz for Nor- mal/Common mode

Noise Filtering EN50991-1

Connections

Output 4*IEC(Battery Power Supply) + 1*Schuko

Computer RS232(DB9) and USB

Display And Diagnostics With LCD and LED Display

LCD Display

Status: Normal, AC Input High, AC Input Low, On Battery, Battery Low, Battery Bad, Over- load, Fault, Phase error, Ground Fault

Data: Utility Voltage, Ouput Voltage, Output Hz, Load%, UPS Temperature, Battery Voltage,

Runtime Timer

LED Display

Green=Normal, Amber=Warning, Red=Critical

LCD shows detalis in respect to the lighting indication of LED

Beeping Alarm

Overload, Fault, High Temperature, Battery On, Battery Low, Battery Bad, Over/Under Voltage,

Frequency Error

Advanced Mode

Self-diagnostic; Direct Time-based readout of

battery remained runtime

Communication Port

USB/DB9 port with TRUE RS232 serial signal

plus dry contact signals

Environmental Condition

0-40°C; 0-95% Non Condensing Humidity

Safety Approval

CE/UL

Dimension (W*H*D cm)

17*24*47

Weight (N.W/ G.W) Kg

26

Codice Ean 80269740062360

All rights registered

Microsoft and Windows are registered trademarks of Micro- soft Corporation

All trade names and marks are registered trademarks of re- spective companies

Specifications are subjected to change without prior notice. No liability for technical errors and/or omissions.

Image 2
Contents 3001 Beeping Alarm PowerBattery Advanced Mode