Atlantis Land A03-OP3000-RC manual Protection, Alarm, Physical, Environment, Computer Interface

Page 19

True On Line Double Conversion UPS

MODEL

1Kva

2Kva

3Kva

PROTECTION

 

 

 

 

Overload

100%~120% delay 60 seconds before switching to

 

 

bypass; 120%~150% delay 10 seconds before

 

 

switching to bypass; >150% immediately switch to

 

 

bypass

 

 

 

Short Circuit

a) Inv. Mode: UPS shutdown and Cut the Output.

 

 

b) Bypass Mode: AC Input fuse Breaks down.

 

Overheat

a) Utility Normal: Switch to Bypass.

 

 

 

b) Utility Abnormal: Buzzer sounds continuously,

 

 

Fault LED lights up then cut the output.

 

High Voltage

Switch to Backup Mode

 

 

Trip-Off

 

 

 

 

Battery Low

Alarm continuously till battery cutoff

 

 

Noise Suppression

Comply with EN50091-2.

 

 

Spike Suppression

Comply with EN61000-4-5.

 

ALARM

 

 

 

 

Audible and Visual

Line Failure, Battery Low, Transfer to Bypass,

 

 

Overload, System Fault Conditions

 

PHYSICAL

 

 

 

 

Dimensions (WxHxD,

482x88x385

482x132x481

482x176x481

 

mm)

2U

3U

4U

 

Net Weight (Kgs)

16

29

39

 

Oulets(IEC/Local)

for detailed information, please refer to Chapter 4.

 

ENVIRONMENT

 

 

 

 

Temperature

0~40

 

 

 

Humidity

30~90% RH Maximum, Non-Condensing

 

Noise

<45 dB (at 1 meter)

 

 

COMPUTER INTERFACE

 

 

 

Interface Type

Standard RS232 Interface

 

 

Protocol

MegaTec RUPS II

 

 

SNMP Adaptability

Yes, Slot for Standard SNMP Card Available

 

Operating Systems

Novell Netware, Windows, OS/2, NetLite, MS-DOS,

 

Compatibility

HP-UX, AIX, SUN OS, UNIX, XENIX. Linux,etc

SAFETY CONFORMANCE

 

 

 

Safety Standard

EN50091-1, cUL

 

 

 

EMC Standard

EN50091-2, EN61000-3-3, EN61000-3-2, FCC Class A

 

Marks

CE, cUL

 

 

34

True On Line Double Conversion UPS

8.2.Supporto Offerto

Per ogni problema con l’UPS consultare questo manuale. Molti problemi potrebbero essere risolti cercando la soluzione del problema nella sezione troubleshooting.

Per qualunque altro problema o dubbio è possibile contattare l’help desk telefonico (02/93907634) gratuito di Atlantis Land che fornirà assistenza da lunedì al giovedì dalle 9:00 alle 13:00 e dalle 14:00 alle 18:00. Il venerdì dalle 9 :00 alle 13 :00. E’ possibile anche utilizzare il fax (02/93906161) la posta elettronica (info@atlantis-land.comoppure tecnici@atlantis-land.com).

AtlantisLand spa Viale De Gasperi 122 20017 Mazzo di Rho(MI)

Tel: 02/93906085 (centralino), 02/93907634(help desk)

Fax: 02/93906161

Email: info@atlantis-land.com oppure tecnici@atlantis-land.com (mettere nell’oggetto il codice del prodotto di cui si chiede assistenza)

WWW:http://www.atlantisland.it o www.atlantis-land.com

Above specifications are subject to change without prior notice. Trademarks of MegaTec, RUPS, IBM, MS-DOS, Novell Netware, Windows, OS/2, NetLite, HP-UX, AIX, SUN, UNIX, and XENIX and Linux are registered trademarks of their respective companies.

35

Image 19
Contents CE Mark Warning AvvertenzeFCC Avviso Importante Capitolo1. Importanti Istruzioni PER LA SicurezzaAvvertimento Caratteristiche Generali Capitolo2. Introduzione al ProdottoCaratteristiche Tecniche Avanzate Capitolo3. Pannello Frontale e Posteriore AC Input DIP SwitchesPanello Posteriore AC InletBaud Rate 2400 bps Data Length Bits Stop Bit Parity None Terminal Block 3KvaPin Porta di comunicazioneRimozione dell’Imballo Capitolo4. Installazione ed AttivazioneScelta del posizionamento dell’unità Installazione Installazione TowerInstallazione Rack Mount Istruzioni per lo stoccaggio Test di operatività e istruzioni per l’installazioneSnmp Slot Sostituzione delle Batterie Rete elettrica presente Capitolo5. Principio di funzionamento dell’UPSMancanza delle Rete Surriscaldamento dell’Inverter Corto circuito in uscita in modalità inverterCorto circuito in uscita in modalità di By-Pass Overload ConditionSituazione Controlli Soluzione Trouble ShootingCapitolo6. Guida alla Manutenzione Modello a BlocchiManutenzione LED\ Install Capitolo7. Guida all’installazione del Software allegatoRups II Installazione Installazione di UPSilonCapitolo8. Appendice Physical AlarmSafety Conformance Protection