American Power Conversion 8000VA Hardwiring, Wiring must be performed by a qualified electrician

Page 4

Hardwiring

Wiring must be performed by a qualified electrician.

1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring.

2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.

3.Remove the access panel (see B).

4.Remove circular knockouts.

5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)

6.Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.

XLT, XLJ, AND XLTW MODELS

Input Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire to L1, L2, and

 

 

.

 

 

 

 

 

 

 

 

 

Wire to L1A, L2A, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

 

Wiring

 

 

 

Voltage

Current

 

External Input Circuit

 

Wire Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load

 

Breaker (typical)

 

(typical)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Nominal)

 

 

 

 

 

 

 

 

 

SURT8000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

40 A

 

 

50 A / 2-pole

 

10mm2

SURT8000XLT,

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

for Input Wiring only

 

#8 AWG

SURT8000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

XLJ-50 A

 

60 A or 63 A / 2-pole

 

16mm2

SURT10000XLT,

 

 

Output

 

 

 

 

 

 

 

XLT-48 A

 

for Input Wiring only

 

#6 AWG

SURT10000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

XLTW-48 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XLI MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase: Wire to L1, N, and

 

 

.

 

 

 

 

Wire to L1A, N1, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-Phase: Wire to L1, L2, L3, N, and

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Wiring

 

Number

 

Voltage

 

Current

 

 

 

External Input

 

Wire Size

 

 

 

 

 

 

 

of

 

 

 

 

Full Load

 

 

 

Circuit Breaker

 

(typical)

 

 

 

 

 

 

 

Phases

 

 

 

 

(Nominal)

 

 

 

(typical)

 

 

SURT8000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

40 A

 

 

 

50 A / 2-pole

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

3+

 

 

 

380/400/415 V

 

15

A / phase when

 

 

 

50 A / 4-pole

 

10mm2

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

A on L1 in bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

40

A

 

 

 

(not required)

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

50 A

 

 

 

63 A / 2-pole

 

16mm2

 

 

Input

 

3+

 

 

 

380/400/415 V

 

18

A / phase when

 

 

 

63 A / 4-pole

 

16mm2

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

A on L1 in bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

50

A

 

 

 

(not required)

 

16mm2

2

Image 4
Contents APC Smart-UPSRT Page Specifications IntroductionUnpacking Removing the BatteriesHardwiring Wiring must be performed by a qualified electricianXLT/XLJ/XLTW Models Page L6-20 L6-30 250V 20A 250V 30A External Battery Pack Connectors Operation On Battery Operation Affect the voltage displayUser Configurable Items XLJ models EPO Emergency Power Off Option Adhere to national and local electrical codes when wiringTerminal Mode to Configure UPS Parameters Replacing the Battery Modules Transporting the UPSTroubleshooting Replace Battery LED flashes Service Limited WarrantyRegulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V ModelsDeclaration of Conformity APC Worldwide Customer Support

8000VA, 200-240 VAC specifications

American Power Conversion (APC), a globally recognized leader in power management, offers a range of high-performance uninterruptible power supplies (UPS), including the 200-240 VAC, 8000VA model. This robust UPS is designed to provide reliable backup power and conditioning for critical systems in various environments, from data centers to industrial applications.

One of the key features of the APC 8000VA UPS is its impressive power capacity. With an output of 8000 VA, it ensures that connected devices remain powered during outages, brownouts, or surges. This UPS can handle a variety of loads, making it versatile for use with servers, networking equipment, and sensitive electronics. Its wide input voltage range of 200-240 VAC allows it to adapt to a variety of power environments, enhancing its usability across different regions and setups.

The APC 8000VA UPS incorporates advanced technologies to ensure optimal performance and efficiency. It uses sine wave output, which provides clean power to sensitive electronics, minimizing the risk of damage and operational disruptions. The smart charging technology ensures efficient battery use, prolonging battery life while maintaining reliable performance. Additionally, the UPS includes intelligent battery management, which continuously monitors battery health and status, providing alerts when maintenance or replacement is needed.

Another hallmark of the APC 8000VA model is its scalability and modular design. Users can expand their backup power solutions easily by adding additional units, making it an excellent choice for growing businesses or varying power needs. The UPS also features multiple outlets for connecting various devices, including standard and high-capacity options, ensuring versatility in powering different types of equipment.

User-friendly monitoring and management are central to the APC UPS experience. It includes an intuitive LCD display that provides real-time information on battery status, load capacity, and input/output voltage, allowing users to make informed decisions about their power systems. Additionally, the UPS can be integrated with APC’s management software, enabling remote monitoring and control for increased convenience and oversight.

In summary, the American Power Conversion 200-240 VAC, 8000VA UPS stands out for its high capacity, advanced technologies, and user-friendly features. Its ability to provide reliable power conditioning and backup makes it an essential component for safeguarding critical infrastructure, ensuring that operations continue smoothly, even in the face of electrical disruptions.