American Power Conversion 990-2485 Operation, Battery LED, Battery module and pair identification

Page 8

Operation

Battery LED

The battery LED is located on the front bezel of the XLBP. During normal operation the LED is not illuminated.

On start-up the XLBP LED may illuminate and blink within the first minute. The LED should then extinquish.

LED Activity

Possible Cause

 

 

XLBP LED illuminates briefly

 

 

 

~ On start-up the XLBP LED may illuminate

Normal operation

and blink within the first minute.

 

~ The XLBP is establishing communication

 

with other components of the system.

 

~ The XLBP is conducting a normal periodic

 

self test

 

 

 

XLBP LED remains illuminated after start-up or illuminates during operation

 

 

XLBP LED is blinking slowly

One or more battery modules are not connected

(one blink per second).

 

 

 

XLBP LED is blinking rapidly

A communication fault exists, check cable connections

(three blinks per second).

 

 

 

The XLBP LED remains illuminated.

~ A potential hardware fault exists contact APC, refer to the Service

 

section in this manual

 

 

Battery module and pair identification

The PowerView will reference XLBP configuration in the following manner.

External Battery Pack

BattPair_1

BattPair_2

Module_1

Module_2

Module_3

Module_4

BattPair_3

BattPair_4

Module_5

Module_6

Module_7

Module_8

8

SURT192RMXLBP2/SURT192XLBP2 6U User Manual

Image 8
Contents APC Smart-UPS→XL Page About this unit Unpack package contentsIntroduction Physical Specifications SpecificationsEnvironmental Specifications Rack-mount configuration InstallationStack configuration Install units in rack Connect UPS and XLBPs Battery LED Battery module and pair identificationOperation LED Activity Possible CauseService Maintenance and Service InformationReplace battery modules Two-Year Warranty Terms of warranty