American Power Conversion SYMF800KH manual IN1

Page 31

Electrical Installation: Relay Board (Optional)

Relay

Name

Events that will trigger the alarm

Mode

Comment

ID

 

 

 

 

 

 

 

 

 

K11

Bypass operation

• UPS is running in normal operation/

Active on

Opr. mode

 

 

bypass operation according to AS400/

 

 

 

 

Novell.

 

 

 

 

 

 

 

K12

Maintenance bypass ON

• The maintenance bypass switch is active.

Active on

Opr. mode

 

 

 

 

 

K13

Stand-by operation

• UPS is in stand-by operation.

Active on

Opr. mode

 

 

 

 

 

K14

Boost charge operation

• UPS is boost charging the batteries.

Active on

Opr. mode

 

 

 

 

 

K15

Fan fault

• Blocked or faulty fan.

Fail safe

Fault

 

 

 

 

 

K16

High equipment

• Static Switch temperature is high;

Fail safe

Warning

 

temperature or inverter

• Main Inverter failure (high temperature

 

 

 

fuse blown

or blown fuse);

 

 

 

 

• Delta Inverter temperature is high;

 

 

 

 

• Magnetics temperature is high;

 

 

 

 

• Isolation Transformer temperature is high

 

 

 

 

(optional);

 

 

 

 

• Battery temperature is high.

 

 

 

 

 

 

 

IN1

Generator active

• System on generator

 

System is

 

 

 

 

running on

 

 

 

 

generator.

 

 

 

 

Battery

 

 

 

 

charging is

 

 

 

 

derated.

 

 

 

 

 

IN2

Battery room ventilation

• Battery room ventilation

 

Ventilation

 

fault

 

 

fault in

 

 

 

 

battery

 

 

 

 

room.

 

 

 

 

Battery

 

 

 

 

charging is

 

 

 

 

off.

 

 

 

 

 

IN3 -

Reserved for future use

 

 

 

IN8

 

 

 

 

 

 

 

 

 

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

25

Image 31
Contents Installation Page Contents Specifications IT Systems Page Symbols used in this guide SafetyInstallation safety Control Section UPS SectionsSerial number Inverter SectionConfiguration 1 Inverter Section placed to the left ConfigurationsConfiguration 2 Inverter Section placed to the right External Bypass Static Switch Electrical Wiring Principle Electrical InstallationInput/Output wiring precautions External disconnection switchesTop Cable Entry Preparing for top cable entry DefaultBattery cable connections top cable entry Top view of Input/Output Section M6 Bolt Cable Entry PE and AC cable connections top cable entry Preparing for bottom cable entry Bottom Cable EntryElectrical Installation Bottom Cable Entry Battery cable connection bottom cable entry Bottom view of Input/Output Section PE and AC cable connections bottom cable entry External Bypass Static Switch Wiring Top cable entry Bottom cable entry Connectionplane 0P0957 Communication cable overviewLocation of optional Relay Board Relay Board OptionalCommunication cables with optional Relay Board Relay Board functions Relay Name Events that will trigger the alarm Mode CommentIN1 Page Low-Impedance/High-Impedance Earthing SpecificationsAC Input Electrical SpecificationsHeat dissipation DC InputAC Output AC Input External Bypass SSWTorque specifications Torque specificationsInput and upstream breakers minimum settings Required Breaker Settings 400 V SystemsOutput and downstream breakers -- minimum settings Specifications Required Breaker Settings 400 V Systems System and Protective Earthing AppendixReference to IEC 60364-5-54 CharacteristicsTN Systems Reference to IEC 60364-4-41Protective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Condition Protective devices in TT systems TT SystemsAppendix TT Systems IT Systems Protective devices in IT systems Is the nominal a C RMS voltage between phase and neutralSee IEC Legal in DK special cases See Breaker Box Q7 Battery Rack Battery Breaker IT installation Page 990-1510D

SYMF800KH specifications

American Power Conversion (APC), a subsidiary of Schneider Electric, is renowned for its expertise in providing reliable power solutions. Among its extensive product lineup, the SYMF800KH stands out as a cutting-edge uninterruptible power supply (UPS) designed to meet the demands of enterprise data centers and critical applications. This model is particularly valued for its impressive performance, adaptability, and advanced technologies.

One of the main features of the SYMF800KH is its capability to deliver an output power of 800 kVA, making it suitable for high-density loads. This UPS operates in a parallel configuration, allowing for scalability by connecting multiple units to provide increased capacity and redundancy. This adaptability ensures that organizations can grow their infrastructure without worrying about power limitations.

Another significant characteristic of the SYMF800KH is its high-efficiency operation that helps reduce energy costs and carbon footprint. With a near-unity power factor and up to 97% efficiency in double conversion mode, the SYMF800KH minimizes energy losses, benefiting both the environment and the organization's operational expenses.

The SYMF800KH is equipped with advanced technologies to ensure maximum reliability and performance. Its innovative SmartBoost and SmartTrim features enhance the UPS's ability to manage input voltage variations and optimize output voltage levels, safeguarding sensitive equipment from potential damage. The unit also boasts an intelligent battery management system, extending battery life and ensuring consistent performance during power outages.

Moreover, the SYMF800KH provides robust monitoring and management options. It is compatible with APC's software solutions, allowing users to monitor real-time data, receive alerts, and conduct remote management from a centralized interface. This feature is critical for maintaining operational reliability and ensuring timely response to any potential power issues.

In addition to its performance capabilities, the SYMF800KH is designed with ease of maintenance in mind. Its modular architecture allows for quick and straightforward replacement of components, minimizing downtime during service activities.

In conclusion, the American Power Conversion SYMF800KH is a high-performance UPS that brings together reliability, efficiency, and advanced technology, making it an ideal choice for organizations seeking to protect their critical infrastructure. By delivering scalable solutions with enhanced management features, the SYMF800KH stands as a top contender in the uninterruptible power supply market. As businesses continue to rely on technology for their daily operations, the importance of such robust power solutions cannot be overstated.