American Power Conversion SYMF800KH manual IT installation

Page 52

 

 

Earthing arrangements and protective conductors - Symmetra MW in

"IT - installation"

 

 

 

 

 

 

 

See:

 

IEC 60364-4-41

§ 413.1.5

 

 

 

 

 

Switchgear

 

 

 

 

 

Q3

 

 

 

Service Entrance

 

 

 

 

 

 

 

 

 

( PDU )

 

 

 

 

 

 

 

 

 

 

 

Residual Current Sense

Residual current protective device

 

 

 

 

 

 

 

 

 

 

 

can be used.

 

 

Q5

 

 

 

 

 

External SSW-Bypass

Q6

 

 

 

 

Bypass - input

 

 

 

Bypass - output

 

 

 

 

 

 

L1

 

 

 

 

L1

 

 

 

 

 

 

 

L2

 

 

 

 

L2

 

 

 

 

 

 

 

L3

 

 

 

 

L3

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

PE

Q4

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

Q1

 

 

 

 

 

Symmetra MW

 

 

 

 

 

 

Mains - input

 

i

Delta

UPS - output

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

L1

 

 

 

i

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

 

i

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

 

 

u

u

 

 

 

 

 

 

 

 

filter

 

 

 

M

 

 

 

 

 

 

 

 

Common-mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

Grounding

Z

 

 

 

 

inverter

 

 

 

 

 

 

impedance

 

 

 

 

 

 

 

 

 

 

Insulation

 

 

 

 

 

 

 

 

 

 

 

 

Monitoring

 

 

 

 

 

 

 

 

 

 

 

 

Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

N

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

Conductor

PE

 

 

 

 

PE

 

 

 

Z

Grounding

 

 

 

 

 

 

 

 

 

 

 

impedance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

-

+

-

 

 

 

 

 

 

Protective Earthing Conductor

Earthing

 

Battery1

 

Battery2

 

 

 

 

 

 

 

( Alternative to earth electrode )

 

 

 

 

 

 

 

 

 

 

Requirement !!

 

 

 

 

 

 

 

 

 

 

 

IEC 60664-4-41

§ 413.1.5.4

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker

 

 

 

 

 

 

 

 

 

 

 

box

Q7

 

 

Q8

 

 

 

 

 

 

Suitable earth electrode: RA x Id

< 50V

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With reference to IEC 60364-4-41

§ 413.1.5.3

 

 

 

 

 

 

 

 

 

 

 

Alternative:

 

 

 

 

 

 

 

 

 

 

 

 

The exposed-conductive-parts can be earthed individually or in groups.

 

 

 

 

 

 

 

 

 

 

But special demands are required. See IEC 60364-4-41 § 413.1.5.5 a)

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

rack

 

 

 

 

 

 

 

 

 

 

 

 

Battery 1

 

Battery 2

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

Image 52
Contents Installation Page Contents Specifications IT Systems Page Safety Symbols used in this guideInstallation safety UPS Sections Serial numberInverter Section Control SectionConfigurations Configuration 1 Inverter Section placed to the leftConfiguration 2 Inverter Section placed to the right External Bypass Static Switch Electrical Installation Electrical Wiring PrincipleExternal disconnection switches Input/Output wiring precautionsPreparing for top cable entry Default Top Cable EntryBattery cable connections top cable entry Top view of Input/Output Section M6 Bolt Cable Entry PE and AC cable connections top cable entry Bottom Cable Entry Preparing for bottom cable entryElectrical Installation Bottom Cable Entry Battery cable connection bottom cable entry Bottom view of Input/Output Section PE and AC cable connections bottom cable entry External Bypass Static Switch Wiring Top cable entry Bottom cable entry Communication cable overview Connectionplane 0P0957Relay Board Optional Location of optional Relay BoardCommunication cables with optional Relay Board Relay Name Events that will trigger the alarm Mode Comment Relay Board functionsIN1 Page Specifications Low-Impedance/High-Impedance EarthingElectrical Specifications AC InputDC Input AC OutputAC Input External Bypass SSW Heat dissipationTorque specifications Torque specificationsInput and upstream breakers minimum settings Required Breaker Settings 400 V SystemsOutput and downstream breakers -- minimum settings Specifications Required Breaker Settings 400 V Systems Appendix System and Protective EarthingCharacteristics TN SystemsReference to IEC 60364-4-41 Reference to IEC 60364-5-54Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsCondition TT Systems Protective devices in TT systemsAppendix TT Systems IT Systems Is the nominal a C RMS voltage between phase and neutral Protective devices in IT systemsSee IEC Legal in DK special cases See Breaker Box Q7 Battery Rack Battery Breaker IT installation Page 990-1510D

SYMF800KH specifications

American Power Conversion (APC), a subsidiary of Schneider Electric, is renowned for its expertise in providing reliable power solutions. Among its extensive product lineup, the SYMF800KH stands out as a cutting-edge uninterruptible power supply (UPS) designed to meet the demands of enterprise data centers and critical applications. This model is particularly valued for its impressive performance, adaptability, and advanced technologies.

One of the main features of the SYMF800KH is its capability to deliver an output power of 800 kVA, making it suitable for high-density loads. This UPS operates in a parallel configuration, allowing for scalability by connecting multiple units to provide increased capacity and redundancy. This adaptability ensures that organizations can grow their infrastructure without worrying about power limitations.

Another significant characteristic of the SYMF800KH is its high-efficiency operation that helps reduce energy costs and carbon footprint. With a near-unity power factor and up to 97% efficiency in double conversion mode, the SYMF800KH minimizes energy losses, benefiting both the environment and the organization's operational expenses.

The SYMF800KH is equipped with advanced technologies to ensure maximum reliability and performance. Its innovative SmartBoost and SmartTrim features enhance the UPS's ability to manage input voltage variations and optimize output voltage levels, safeguarding sensitive equipment from potential damage. The unit also boasts an intelligent battery management system, extending battery life and ensuring consistent performance during power outages.

Moreover, the SYMF800KH provides robust monitoring and management options. It is compatible with APC's software solutions, allowing users to monitor real-time data, receive alerts, and conduct remote management from a centralized interface. This feature is critical for maintaining operational reliability and ensuring timely response to any potential power issues.

In addition to its performance capabilities, the SYMF800KH is designed with ease of maintenance in mind. Its modular architecture allows for quick and straightforward replacement of components, minimizing downtime during service activities.

In conclusion, the American Power Conversion SYMF800KH is a high-performance UPS that brings together reliability, efficiency, and advanced technology, making it an ideal choice for organizations seeking to protect their critical infrastructure. By delivering scalable solutions with enhanced management features, the SYMF800KH stands as a top contender in the uninterruptible power supply market. As businesses continue to rely on technology for their daily operations, the importance of such robust power solutions cannot be overstated.