American Power Conversion UPS user manual User Configurable Items

Page 10

USER CONFIGURABLE ITEMS

NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE, OPTIONAL HARDWARE, OR

CONFIGURATION IN TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-

Every 14 days

Every 7 days

This function sets the interval at which the

Test

(336 hours)

(168 hours),

UPS will execute a self-test. Refer to your

 

 

On Startup Only,

software manual for details.

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight charac-

Use this field to uniquely identify the UPS

 

 

ters to define the

for network management purposes.

 

 

UPS

 

 

 

 

 

Date of Last Bat-

Manufacture

Date of Battery

Reset this date when you replace the battery

tery Replacement

Date

Replacement

pack.

 

 

 

 

Minimum Capacity

0 percent

15, 25, 35, 50, 60,

The UPS will charge its batteries to the

Before Return from

 

75, 90 percent

specified percentage before return from a

Shutdown

 

 

shutdown.

 

 

 

 

Duration of Low

2 minutes

5, 7, 10, 12, 15, 18,

This function sets the time before shutdown

Battery Warning

 

20 minutes

at which the UPS issues a low battery

 

 

 

warning. Set it higher than the default if the

 

 

 

operating system needs more time for shut-

 

 

 

down.

 

 

 

 

Alarm Delay After

5 second delay

30 second delay, At

Set the alarm delay to avoid alarms for

Line Fail

 

Low Battery Condi-

minor power glitches.

 

 

tion, No Alarm

 

 

 

 

 

Shutdown Delay

20 seconds

0, 60, 120, 240, 480,

This function sets the interval between

 

 

720, 960 seconds

when the UPS receives a shutdown com-

 

 

 

mand and when shutdown occurs.

 

 

 

 

Synchronized

0 seconds

20, 60, 120, 240,

The UPS will wait the specified time after

Turn-on Delay

 

480, 720, 960 sec-

the return of utility power before turn-on

 

 

onds

(for example, to avoid branch circuit over-

 

 

 

load).

 

 

 

 

Output Voltage

230 VAC

240, 220, 225 VAC

Nominal output voltage setting.

Setting

 

 

 

 

 

 

 

High Transfer

+ 10% of output

+5%, +15%, +20%

Maximum voltage that the UPS will pass to

Point

voltage setting

 

the load during internal bypass operation.

 

 

 

 

Low Transfer Point

-30% of output

-20%, -25%,

Minimum voltage that the UPS will pass to

 

voltage setting

-15%

the load during internal bypass operation.

 

 

 

 

990-1137A, 01/03

8

Image 10
Contents APC Smart-UPSRT UX Page Installation PlacementAmp Fuse Volt System Click on Configuration Click on UPS Operating Parameters Cold Start Load Power OffOperation Auto Matic Self Test ManualOnline Utility Voltage Battery Equipment from its batteriesBypass Battery Charge Over Load Replace Battery On Battery Operation User Configurable Items Terminal Mode TRANSPORT, MAINTENANCE, and Troubleshooting Troubleshooting Service CONTACT, REGULATORY, and Warranty Information Refer to the information provided at the APC Internet siteLimited Warranty