American Power Conversion UPS user manual Amp Fuse Volt System

Page 4

2.CONNECT THE EXTERNAL BATTERIES

Battery

 

 

Connector

Step A

Step B

On Rear

 

 

Panel

 

 

1.Refer to www.apc.com/support for the Smart- UPS RT Battery Pack User Manual (990- 1083A).

2.If using a non-APC battery pack, a 48V battery string should be wired to the UPS using the en- closed battery cable assembly.

Batteries must be Sealed Lead-Acid type.

Each string of four 12V batteries must be provided with an 80-100 amp fuse or fuse- able link to protect in the event of a short circuit.

80-100 Amp Fuse

48 Volt System

3.CONNECT THE EQUIPMENT TO THE UPS AND CONNECT THE UPS TO THE AC POWER SUPPLY

1.On the back panel, plug the female end of the power cord into the receptacle. Then plug the male end into a two-pole, three-wire, grounding receptacle. Avoid using extension cords and adapter plugs.

2.Connect the equipment to the UPS using the power cords provided with the equipment.

3.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, be sure all con- nected equipment is switched on. The equipment will not be powered until the UPS is turned on.

4.TURN ON THE UPS

Make sure the battery is connected before turning on the UPS! Press the button on the front panel to power up your UPS. This will power up connected equipment if that equipment is turned on.

The UPS charges the batteries when it is connected to utility power. Do not expect full run time during this initial charge period. Time depends on number and type of batter- ies.

The unit performs a self-test automatically when turned on and every two weeks thereafter (by de- fault). Refer to the User Configurable Items section of this manual, below, for details on changing the default interval.

To turn on the UPS when no utility power is present, see the Cold Start function in the Operations section of this manual.

990-1137A, 01/03

2

Image 4
Contents APC Smart-UPSRT UX Page Installation PlacementAmp Fuse Volt System Click on Configuration Click on UPS Operating Parameters Power Off OperationCold Start Load Auto Matic Self Test ManualOnline Utility Voltage Battery Equipment from its batteriesBypass Battery Charge Over Load Replace Battery On Battery Operation User Configurable Items Terminal Mode TRANSPORT, MAINTENANCE, and Troubleshooting Troubleshooting Service CONTACT, REGULATORY, and Warranty Information Refer to the information provided at the APC Internet siteLimited Warranty