American Power Conversion UXI/UXICH user manual Connect the EPO Emergency Power OFF Option

Page 13

CONNECT THE EPO (EMERGENCY POWER OFF) OPTION

The output power can be disabled in an emergency by closing a switch connected to the EPO.

Adhere to national and local electrical codes when wiring the EPO.

Wiring must be performed by a qualified electrician.

EPO switch

The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.

The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC standard).

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.

If circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the UPS to the EPO switch:

CL2: Class 2 cable for general use

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with local regulations.

11

Image 13
Contents APC Smart-UPSRT UXI/UXICH Page Introduction Page Normal bypass Battery Safety Connect the Ground and Wire the Battery System Avoid using extension cords Operation Cold Start User Configurable Items Low Bypass Point Connect the EPO Emergency Power OFF Option Terminal Mode to Configure UPS Parameters Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support