ATTACH THE BEZEL TO THE UPS
HARDWIRING INSTRUCTIONS 5000 VA MODELS ONLY:
•Wiring must be performed by a qualified electrician.
•Adhere to all national and local electrical codes.
•Install a high magnetic 30/32 A utility circuit breaker
•Use #10 AWG gauge (5 mm2) wire.
1.Switch the utility circuit breaker OFF.
2.Remove the input access panel.
3.Remove circular knockout.
4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not included).
5.Replace the access panel.
2