Introduction
Electrical Specifications
Attention:
•Operation above the input voltage range may cause equipment damage.
•Operation below the input voltage range may cause overload or automatic shutdown. When connecting directly to a branch circuit, check that the line voltage is within specifications. When connecting to the UPS, check that the line voltage into the UPS is within specifications before transferring to bypass mode.
Note: In order for AP9626 models to output the full 5000 VA, the input must be hardwired to a 5500 VA source.
Installation | With Line Cord |
| With Hardwire |
| (AP9826 or AP9627) |
| (AP9626 or AP9628) |
Nominal Input Voltage |
| 208 Vac | |
Nominal Output Voltage |
| 120 Vac | |
Input Voltage Range |
| ||
Input Current Rating | 24 A |
| 26 A |
Line Frequency |
| 60 Hz | |
Efficiency |
| ||
Maximum Input Power | 5000 VA |
| 5500 VA |
Maximum Output Power | 4500 VA |
| 5000 VA |
|
|
|
|
*For continuous operation below Vin = 205 Vac, the output load must be reduced to limit the maximum input current to the amount specified above. Continuous operation above the maximum specified input current may cause the unit to overheat and shut down. Please contact APC for additional information.
**Not available for AP9627.
Model | AP9626 | AP9627 | AP9628 | |
Input Power | 3 ft cord with | 2 ft cord with | Hardwire | |
Distribution | hardwired |
|
|
|
Output Power | (2) 15 A circuits with | (4) | 20 A circuits with | Hardwire |
Distribution | (4) | (4) |
| |
| with |
|
|
|
4 | APC |