5:TROUBLESHOOTING

Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with complex UPS problems.

PROBLEM AND/OR POSSIBLE

SOLUTION

CAUSE

 

UPS WILL NOT TURN ON

 

UPS not connected to utility

Check that the power cord from the UPS to the utility power supply is se-

power supply.

curely connected at both ends.

 

 

Battery not connected prop-

Check that battery connector on the rear panel is fully snapped into position.

erly.

 

 

 

Very low or no utility voltage.

Check the utility power supply to the UPS by plugging in a table lamp. If the

 

light is very dim, have the utility voltage checked.

 

 

UPS WILL NOT TURN OFF

 

Internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS, unplug the battery connec-

 

tor on the rear panel, and have it serviced immediately.

 

 

UPS BEEPS OCCASIONALLY

 

Normal operating UPS beeps

None. The UPS is protecting the connected equipment from occasional util-

when running on battery.

ity power irregularities.

 

 

UPS IS NOT PROVIDING EXPECTED BACKUP TIME

The UPS battery is weak due

Charge the battery. Batteries require recharging after extended outages, and

to a recent outage or is near

wear faster when frequently put into service or when operated at elevated

the end of the service life.

temperatures. If the battery is near the end of the service life, consider re-

 

placing even if the replace battery LED is not yet illuminated.

 

 

LEFT HALF, RIGHT HALF, OR CENTER SECTION OF FRONT PANEL LEDS ARE FLASHING

Internal UPS fault. The UPS

Do not attempt to use the UPS. Turn off the UPS, unplug the battery connec-

has shut down.

tor on the rear panel, and have it serviced immediately.

 

 

FRONT PANEL LEDS FLASH SEQUENTIALLY

The UPS has been shut down

None. The UPS will restart automatically when utility power returns.

remotely through software or

 

an optional accessory card.

 

 

 

ALL LEDS ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET

The UPS is shut down or the

None. The UPS will return to normal operation when the power is restored

battery is discharged from an

and the battery has a sufficient charge.

extended outage.

 

 

 

8

Image 10
Contents APC Smart-UPS Page Introduction Connect the BatteryInstallation UnpackConnect Equipment and Power to the UPS Rear Panels 100V/120V230V Basic ConnectorsFront Display Panel OperationBattery Operation Affect the voltage displayUser Configurable Items UPS ID Upsiden230V model Storage Battery Module MaintenanceSTORAGE, MAINTENANCE, and Shipping ShippingTroubleshooting Replace BATTERY/BATTERY Disconnected LED is Illuminated Service Contact Information100V/120V models Regulatory and Warranty Information230V models Limited Warranty