3:USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
Automatic Self- | Every 14 days | Every 7 days | Set the interval at which the UPS will | |
Test | (336 hours) | (168 hours), | execute a | |
|
| On Startup Only, |
| |
|
| No |
| |
|
|
|
| |
UPS ID | UPS_IDEN | Up to eight charac- | Uniquely identify the UPS, (i.e. server | |
|
| ters (alphanumeric) | name or location) for network man- | |
|
|
| agement purposes. | |
|
|
|
| |
Date of Last Bat- | Manufacture Date | mm/dd/yy | Reset this date when you replace the | |
tery Replacement |
|
| battery module. | |
|
|
|
| |
Minimum Capacity | 0 percent | 0, 15, 30, 45, 50, 60, | Specify the percentage to which batter- | |
Before Return from |
| 75, 90 percent | ies will be charged following a low- | |
Shutdown |
|
| battery shutdown before powering | |
|
|
| connected equipment. | |
|
|
|
| |
Voltage Sensitivity | High | High sensitivity, | Note: In situations of poor power qual- | |
The UPS detects |
| Medium sensitivity, | ity, the UPS may frequently transfer to | |
| Low sensitivity | battery operation. If the connected | ||
and reacts to line |
| |||
|
| equipment can operate normally under | ||
voltage distortions |
|
| ||
|
| such conditions, reduce the sensitivity | ||
by transferring to |
|
| ||
|
| setting to conserve battery capacity | ||
battery operation to |
|
| ||
|
| and service life. | ||
protect connected |
|
| ||
|
|
| ||
equipment. |
|
|
| |
|
|
|
| |
Alarm Delay Con- | Enable | Enable, Mute, Dis- | Mute ongoing alarms or disable all | |
trol |
| able | alarms permanently. | |
|
|
|
| |
Shutdown Delay | 90 seconds | 0, 90, 180, 270, 360, | Set the interval between the time when | |
|
| 450, 540, 630 sec- | the UPS receives a shutdown com- | |
|
| onds | mand and the actual shutdown. | |
|
|
|
| |
Low Battery Warn- | 2 minutes | 2, 5, 8, 11, 14, 17, | The UPS will beep when 2 minutes of | |
ing | PowerChute soft- | 20, 23 minutes | battery runtime remains. | |
|
|
| ||
| ware provides | (Times are approxi- | Change the low battery warning inter- | |
| automatic, unat- | mate.) | val setting to the time that the operat- | |
| tended shutdown |
| ing system or system software requires | |
| when approxi- |
| to safely shut down. | |
| mately 2 minutes |
|
| |
| of battery oper- |
|
| |
| ated runtime re- |
|
| |
| mains. |
|
| |
|
|
|
| |
Synchronized | 0 seconds | 0, 60, 120, 180, 240, | Specify the time the UPS will wait | |
| 300, 360, 420 sec- | after the return of utility power before | ||
|
| onds | ||
|
|
| load). | |
|
|
|
| |
|