APC PDPM150G6F Recommended conductor sizes, Table for 40C, Ambient/4CCC 480208 600208 480415

Page 25

Recommended conductor sizes

Note: All wiring must comply with all applicable national and or local electrical codes.

Conductor sizing in this manual is based on Table 310-16 of the 2011 National Electrical Code (NEC) with the following assertions:

90°C conductors (THHN) for 75°C termination

3 Current Carrying Conductors for Unit Input Circuit Breaker and 4 Current Carrying Conductors for Subfeed Circuit Breaker

An ambient temperature of 30°C

Two conduits for each subfeed

One Equipment Grounding Conductor for each conduit

If the ambient room temperature is greater than 30°C, larger conductors are to be selected in accordance with the correction factors of the NEC.

Equipment Grounding Conductors (EGC) are sized in accordance with NEC Article 250-122 and Table 250-122.

Grounding Electrode Conductors (GEC) are sized in accordance with NEC Article 250-66 and Table 250-66.

The conductor sizes are recommendations for maximum configurations. Even if the load is less than the maximum rating, it is wise to plan for future load increases. If the system is operated at a lower load than its rating and it is desired to supply the system with a lower rated breaker and smaller conductors, conductor ampacities are to be selected in accordance with the NEC. The transformer inrush must be taken into account when sizing conductors.

Table for 40°C

PDPM150G6F

PDPM150L6F

PDPM175G6H

ambient/4CCC

480:208

600:208

480:415

 

 

 

 

Mains Input Φ

Cu only: 250kcmil

Cu only: 3/0 AWG

Cu: 350kcmil

 

Al: 500kcmil

 

75°C conductor minimum

90°C conductor minimum

 

75°C conductor minimum

 

 

 

 

 

 

 

Equipment

Cu: 4 AWG

Cu: 6 AWG

Cu: 4 AWG

Grounding

 

 

Al: 2 AWG

Conductor (EGC)

 

 

 

 

 

 

 

Grounding

Cu: 2 AWG

Cu: 2 AWG

Cu: 2 AWG

Electrode

 

 

Al: 1/0 AWG

Conductor (GEC)

 

 

 

Output

Supplied with Power Distribution Modules

 

 

 

 

 

Subfeed Output

Cu only: (2) 300kcmil Φ and

Cu only: (2) 300kcmil Φ and

Cu: (2) 2/0 AWG Φ and N, 4

 

N, 3 AWG EGC, GEC not

N, 3 AWG EGC, GEC not

AWG EGC, GEC not

 

required.

required.

required.

 

90°C conductor minimum

90°C conductor minimum

Al: (2) 4/0 AWG Φ and N, 2

 

 

 

AWG EGC, GEC not

 

 

 

required.

 

 

 

75°C conductor minimum

 

 

 

 

150/175kw Modular PDU Installation

21

Image 25
Contents Installation Page Contents Options Overview Important Safety InformationPlease Note DisclaimerOperation and Adjustments Additional Safety InformationBefore you begin Related Documents Product Related Information About This ManualUser Comments Electrical Safety InstallationInrow Installation Connect and Level Enclosures Perform Equipotential BondingTop entry installation Install Input Power CablesFor PDPM150L6F For PDPM150G6FSidecar Model Bottom entry installationTo PDU Install Subfeed Cables Install User Input/Output Contacts 150/175kw Modular PDU Installation Install the Communication Cable Installation Power Distribution Modules PDMsInstall filler plates Remove power distribution modules PDMsShielding Troughs OptionsSeismic Stability Kit Install rear anchoring bracketsInstall front anchoring bracket AC Input SpecificationsAC Output Environment and Compliance Distribution TransformerTable for 40C Recommended conductor sizesAmbient/4CCC 480208 600208 480415 Table for 30C Regulatory Agency ApprovalAmbient/4CCC 600208 480415Canada-ICES Radio Frequency Interference990-4384 2012 APC Worldwide Customer Support

175kW, PDPM150G6F, PDPM175G6H, 150, PDPM150L6F specifications

The APC PDPM150L6F, PDPM175G6H, and PDPM150G6F are high-performance power distribution modules designed for specialized applications requiring reliable and efficient power management. With a power output of 150 kW and 175 kW respectively, these modules are engineered to meet the demands of modern data centers, industrial setups, and critical infrastructure.

One of the standout features of the APC PDPM series is its robust design, ensuring durability and longevity in challenging conditions. The modular architecture allows for flexible configuration and easy scalability, enabling users to adjust their power distribution needs as their operations grow. This adaptability is ideal for environments where power requirements fluctuate or expand over time.

The PDPM series utilizes advanced power management technologies that enhance efficiency and minimize energy loss. These modules incorporate intelligent load management systems that optimize power distribution, ensuring balanced loads across all connected devices. This not only improves overall system performance but also extends the lifespan of equipment by preventing overload conditions.

Another key characteristic of the APC PDPM150L6F, PDPM175G6H, and PDPM150G6F is their high reliability. Each unit is designed with redundant components and advanced monitoring capabilities, allowing for real-time diagnostics and alerts. This proactive approach ensures that potential issues are identified and addressed before they can impact operations, significantly reducing downtime.

Additionally, the user-friendly interface of these modules facilitates easy setup and configuration. Operators can quickly access essential information, including power usage data and system status, enhancing operational transparency. The integration of intelligent software tools further simplifies management tasks and enables remote monitoring, making it easier for facility managers to maintain optimal performance levels.

In summary, the APC PDPM150L6F, PDPM175G6H, and PDPM150G6F power distribution modules stand out for their efficiency, reliability, and scalability. Equipped with advanced technologies and designed for ease of use, these modules are an excellent choice for businesses looking to enhance their power management capabilities in an increasingly demanding technological landscape. Whether for data centers or critical infrastructure, the PDPM series delivers the performance that modern operations require.