APC PDPM150L6F, PDPM150G6F Regulatory Agency Approval, Table for 30C, Ambient/4CCC, 600208 480415

Page 26

Table for 30°C

PDPM150G6F

PDPM150L6F

PDPM175G6H

ambient/4CCC

480:208

600:208

480:415

 

 

 

 

Mains Input Φ

Cu: 4/0 AWG

Cu only: 3/0 AWG

Cu: 300kcmil

 

A1: 300kcmil

Al: 400kcmil

 

90°C conductor minimum

 

75°C conductor minimum

75°C conductor minimum

 

 

 

 

 

 

Equipment

Cu: 4 AWG

Cu: 6 AWG

Cu: 4 AWG

Grounding Conductor

A1: 2 AWG

 

Al: 2 AWG

(EGC)

 

 

 

 

 

 

 

Grounding Electrode

Cu: 2 AWG

Cu: 2 AWG

Cu: 2 AWG

Conductor (GEC)

A1: 1/0 AWG

 

Al: 1/0 AWG

 

 

 

 

Output

Supplied with Power Distribution Modules

 

 

 

 

 

Subfeed Output

Cu: (2) 250kcmil Φ and N,

Cu: (2) 250kcmil Φ and N,

Cu: (2) 2/0 AWG Φ and N,

 

3 AWG EGC, GEC not

3 AWG EGC, GEC not

4 AWG EGC, GEC not

 

required.

required.

required.

 

Al: (2) 350 kcmil Φ and N,

Al: (2) 350 kcmil Φ and N,

Al: (2) 3/0 AWG Φ and N,

 

1 AWG EGC, GEC not

1 AWG EGC, GEC not

2 AWG EGC, GEC not

 

required.

required.

required.

 

90°C conductor minimum

90°C conductor minimum

75°C conductor minimum

 

 

 

 

Φ= phase, N = neutral

(2) = two conductors per phase and neutral (when neutral is required)

Subfeed is required to have two conductors per phase & N for full output due to limited wire bend space Cu= Copper conductors, Al= Aluminum conductors

CCC = Current Carrying Conductor

Regulatory Agency Approval

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC and ICES-003 Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Guide, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.

22

150/175kw Modular PDU Installation

Image 26
Contents Installation Page Contents Options Important Safety Information OverviewDisclaimer Please NoteBefore you begin Additional Safety InformationOperation and Adjustments User Comments About This ManualRelated Documents Product Related Information Inrow Installation InstallationElectrical Safety Perform Equipotential Bonding Connect and Level EnclosuresFor PDPM150L6F Install Input Power CablesTop entry installation For PDPM150G6FBottom entry installation Sidecar ModelTo PDU Install Subfeed Cables Install User Input/Output Contacts 150/175kw Modular PDU Installation Install the Communication Cable Power Distribution Modules PDMs InstallationRemove power distribution modules PDMs Install filler platesOptions Shielding TroughsInstall rear anchoring brackets Seismic Stability KitInstall front anchoring bracket AC Output SpecificationsAC Input Distribution Transformer Environment and ComplianceAmbient/4CCC 480208 600208 480415 Recommended conductor sizesTable for 40C Ambient/4CCC Regulatory Agency ApprovalTable for 30C 600208 480415Radio Frequency Interference Canada-ICESAPC Worldwide Customer Support 990-4384 2012

175kW, PDPM150G6F, PDPM175G6H, 150, PDPM150L6F specifications

The APC PDPM150L6F, PDPM175G6H, and PDPM150G6F are high-performance power distribution modules designed for specialized applications requiring reliable and efficient power management. With a power output of 150 kW and 175 kW respectively, these modules are engineered to meet the demands of modern data centers, industrial setups, and critical infrastructure.

One of the standout features of the APC PDPM series is its robust design, ensuring durability and longevity in challenging conditions. The modular architecture allows for flexible configuration and easy scalability, enabling users to adjust their power distribution needs as their operations grow. This adaptability is ideal for environments where power requirements fluctuate or expand over time.

The PDPM series utilizes advanced power management technologies that enhance efficiency and minimize energy loss. These modules incorporate intelligent load management systems that optimize power distribution, ensuring balanced loads across all connected devices. This not only improves overall system performance but also extends the lifespan of equipment by preventing overload conditions.

Another key characteristic of the APC PDPM150L6F, PDPM175G6H, and PDPM150G6F is their high reliability. Each unit is designed with redundant components and advanced monitoring capabilities, allowing for real-time diagnostics and alerts. This proactive approach ensures that potential issues are identified and addressed before they can impact operations, significantly reducing downtime.

Additionally, the user-friendly interface of these modules facilitates easy setup and configuration. Operators can quickly access essential information, including power usage data and system status, enhancing operational transparency. The integration of intelligent software tools further simplifies management tasks and enables remote monitoring, making it easier for facility managers to maintain optimal performance levels.

In summary, the APC PDPM150L6F, PDPM175G6H, and PDPM150G6F power distribution modules stand out for their efficiency, reliability, and scalability. Equipped with advanced technologies and designed for ease of use, these modules are an excellent choice for businesses looking to enhance their power management capabilities in an increasingly demanding technological landscape. Whether for data centers or critical infrastructure, the PDPM series delivers the performance that modern operations require.