American Power Conversion 240-320kW400V Stop/Start UPS and Operating the External Service Bypass

Page 4

Stop/Start UPS and Operating the External Service Bypass

2.0Stop/Start UPS and Operating the External Service Bypass Panel

WARNING!

AC voltage generated either from batteries or mains may be present at UPS output.

Always disconnect AC input supply source, switch off UPS, AND switch off DC.

TEST BEFORE YOU TOUCH!

Some UPS systems have a factory-set autostart feature, automatically switching on UPS whenever mains supply is switched on (AC line). See section 4.0 Parameter settings for instructions on how to switch off this function.

Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed. Prior to being serviced, the APC Silcon UPS must be left in shut-down mode for a minimum of 5 minutes.

CAUTION!

Refer to the Maintenance & Testing section in this guide if the UPS is to be taken out of operation for more than 48 hours.

Users without electrical qualifications may switch UPS to and from stand-by-mode/normal operation, following instructions below. (In stand-by mode, the UPS has no output voltage).

2.1Stop UPS (for stand-by)

CAUTION!

If the UPS system is equipped with a service bypass panel, and if the load must remain energized by mains, refer to the Operating Service Bypass Panel sections in this guide before proceeding

Action

Open the front door and activate the "ON" and "OFF" push-button simultaneously

Display shows

Description

 

Alarm LED lights.

System off

Acoustic alarm sounds

 

for 30 seconds

2.2Start UPS (from stand-by)

Action

Open the front door and activate the green and "ON" push button

Display shows

Normal operation Load power xx%

990-4057

4

User Guide APC Silcon 240-320kW 400V UPS

Image 4
Contents 240-320kW400V UPS User Guide Copyright 2001 APC JapanUser Guide APC Silcon 240-320kW 400V UPS Thank YouIntroduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassStart UPS from stand-by Stop UPS for complete power down Switching off the UPSSystem OFF Start UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesEconomy Mode Parameter Settings Parameter SettingsParameter Settings Programming Keys Switching to Bypass OperationProgramming Example To return to normal operation Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionAlarms and Events Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkHow to Contact APC