American Power Conversion 240-320kW400V manual System OFF

Page 6

Stop/Start UPS and Operating the External Service Bypass

1.Open front doors

2.Note that step 3 will interrupt output voltage and activate the alarm! The red LED alarm below the display will light up

The acoustic alarm will sound for 30 seconds*

3.Press the green ON and the red OFF button simultaneously. The red LED alarm below the display will light up

The acoustic alarm will sound for 30 seconds*

4.On systems with no Service Bypass Panel, switch off the mains supply

5.The red LED alarm below the display will light up The acoustic alarm will sound for 30 seconds

6.Switch off battery breakers F001 and F002 in the Battery Breaker Box or battery cabinet

Refer to LED indication and labelling in Battery Breaker Box or battery cabinet

7.To switch off mains supply, open Q001 – on systems with Service Bypass Panel.

Display shows

**System OFF**

**System OFF**

8. The acoustic alarm sounds

Blank

*Reset the acoustic alarm by pressing .

The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out.

CAUTION!

Recharge batteries out of service every 3 months to prevent damage.

WARNING!

Internal DC capacitor may contain energy even after the UPS has been switched off. Allow for automatic discharge by waiting at least 5 minutes after switching off UPS and battery breakers before working on the UPS.

990-4057

6

User Guide APC Silcon 240-320kW 400V UPS

Image 6
Contents 240-320kW400V UPS User Guide Copyright 2001 APC JapanUser Guide APC Silcon 240-320kW 400V UPS Thank YouIntroduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Stop UPS for complete power down Switching off the UPSSystem OFF Start UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesEconomy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example To return to normal operation Displaying the Alarm Stack Alarms and EventsAlarms and Events Mode CommentsPossible Alarms Alarms Description ActionAlarms and Events Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Corporate How to Contact APCHow to Contact APC APC DenmarkHow to Contact APC