American Power Conversion 480kW manual Programming Keys, Switching to Bypass Operation

Page 23

Parameter Settings

4.1Programming Keys

Displays time

Return to normal window

Accesses the alarm stack

Scrolls up through list

Scrolls down through list

Stores parameters/enters parameter stack

Silences the audible alarm

Chooses or changes parameters

4.2Switching to Bypass Operation

Programming Example

Action

 

 

Display shows

1.

Press

to enter parameter stack

 

2.

Press

or

until

Bypass operation

: NO

3.

Press

until

 

Bypass operation

 

: YES

 

 

 

 

4.

Press

to store

 

 

5.

Press

to exit

 

Bypass operation

 

 

 

 

 

990-4058GB

User Guide APC Silcon 480kW 400/415V UPS

23

Image 23
Contents Copyright 2002 APC Japan 480kW 400/415V UPS User GuideThank You User Guide APC Silcon 480kW 400/415V UPSContents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Switching off the UPS Stop UPS for complete power downSystem OFF UPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Display of Measured Values Using the Remote DisplayEconomy Mode Parameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Normal operation Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsAlarms and Events Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil Battery capacity Test Xxx Press Data stored APC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Denmark How to Contact APCHow to Contact APC APC Corporate