APC 5000RMB user manual Operating Instructions

Page 14

Operating Instructions

Switch On — Switch Off

With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The loads are immediately powered while the UPS beeps and performs a self-test.

Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS as a master on/off switch for the protected equipment.

Note:

Whenever the UPS is plugged in and utility voltage is present, the charger maintains battery charge.

The on-line LED illuminates when the UPS is supplying utility power to the loads.

On Battery

During on-battery operation, the on-battery LED illuminates and the UPS sounds an audible alarm consisting of four beeps every 30 seconds. The alarm stops when the UPS returns to on-line operation.

Battery Charge Bar Graph

100%

80%

60%

40% 20%

The 5-LED display on the right of the front panel shows the present charge of the UPS’s battery as a percentage of the battery’s capacity. When all five LEDs light, the battery is fully charged. The top LED goes out whenever the battery is not 100% charged. When the lowest LED is flashing, the battery can supply less than two minutes of run time for the load. The battery capacity threshold is shown in the figure to the left (values are not listed on the UPS).

Shutdown Mode

In shutdown mode the UPS stops supplying power to the load, waiting for the return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface or the accessory slot can command the UPS to shut down. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. The UPS will scroll the front panel indicators sequentially in shutdown mode.

Self-test

The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). Automatic self- test eases maintenance requirements by eliminating the need for periodic manual self-tests.

During the self-test, the UPS briefly operates the loads on-battery. If the UPS passes the self-test, it returns to on-line operation.

If the UPS fails the self-test it immediately returns to on-line operation and lights the replace battery LED.

The loads are not affected by a failed test. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, replace the battery using the procedure in Replacing the Battery, page 10.

Replace Battery

If the battery fails a self-test, the UPS emits short beeps for one minute and the replace battery LED illuminates. The UPS repeats the alarm every five hours. Perform the self-test procedure to confirm replace battery conditions. The alarm stops when the battery passes the self-test.

8

Image 14
Contents 990-7080B 09/00 990-7080B 09/00 Replacement and Recycling of Batteries Handling SafetyElectrical Safety Page Table of Contents Page Introduction ContentsHow to Unpack the SU 5000 UPS UnpackingInstalling the SU5000RMB InstallationPlacement Position the UPSInstall the Mounting Rails in the Rack Vac Units with Line Cord Connect Input Power to the UPSVac Units Vac Units for Hard Wire Install PowerChute and Accessories Install the BatteriesPower up the UPS and Accessories Connect Equipment to the UPSInitial Startup Operating Instructions Overload Low BatteryLoad Bar Graph SmartTrimReplacing the Battery Battery Replacement ProcedureStorage Conditions User Configuration ItemsStorage Extended storageOn-Battery Run Time Specifications Troubleshooting Problem and Possible Cause Solution UPS will not turn onAPC Contact Information ServiceLimited Warranty Radio Frequency Interference 200/208 Vac UnitsVac Units Appendix B Transporting Your Smart-UPS