APC 5000RMB user manual Specifications

Page 19

Specifications

 

200/208 Vac

 

 

230 Vac

Acceptable input voltage

0 – 325 Vac

Input voltage (on-line operation)

160 – 253 Vac

 

 

174 – 286 Vac

208 volt output range

177 – 229 Vac

 

 

196 – 253 Vac

Nominal input frequency

50 or 60 Hz, autosensing

Input protection

Resettable circuit breaker

Frequency limits (on-line operation)

47 to 63 Hz

Transfer time

3 ms typical, 6 ms maximum

Maximum load, total

5000 VA/3750 W

On-battery output voltage

208 Vac

 

 

220, 225, 230, or 240 Vac

On-battery frequency

50 or 60 Hz, ñ0.1 Hz;

 

unless synchronized to utility during brownout

On-battery waveshape

Low-distortion sine wave

Overload protection (on-battery)

Overcurrent and short-circuit protected, latching shutdown on overload

Overload protection (on-line)

2 pole, 20 A UL certified input

 

Not applicable

 

circuit breaker

 

 

Surge energy rating

 

 

 

 

(one time, 10/1000 æs waveform)

1120 J

 

Surge current capability

 

 

 

 

(one time, 8/20 æs waveform)

6500 A maximum

Surge response time

0 ns (instantaneous) normal mode;

 

<5 ns common mode

Surge voltage let-through

 

 

 

 

(percentage of applied ANSI C62.41

0.30%

 

Cat. A ñ6 kV test waveform)

 

 

 

 

Noise filter

Normal and common mode EMI/RFI suppression,

 

100 kHz to 10 MHz

Battery type

Spill proof, maintenance free, sealed lead-acid

Typical battery life

3 to 6 years, depending on number of discharge cycles

 

and ambient temperature

Typical recharge time

2 to 5 hours from total discharge

Operating temperature

0 to 40§C (+32 to +104§F)

Storage temperature

-15 to +45§C (+5 to +113§F)

Operating and storage relative humidity

0 to 95%, non-condensing

Operating elevation

0 to +3,000 m (0 to +10,000 ft.)

Storage elevation

0 to +15,000 m (0 to +50,000 ft.)

Electromagnetic Compatibility (EMC)

61000-4-2, 61000-4-3, 61000-4-4,

 

 

61000-2-2, 61000-3-2,

 

61000-4-5

 

 

EN61000-4-1, EN61000-4-11

 

FCC/DOC Class A verified

 

EN55022 Class A, EN50091-2

Audible noise at 1 m (3 ft.)

<55 dBA

Safety approvals

Listed to UL 1778, certified to CSA

 

GS licensed by VDE to

 

107.1

 

 

EN50091-1-1 and EN60950

Size (W x H x D)

17.0 x 8.7 x 24.5 in.

 

43.2 x 19.6 x 62.2 cm

Weight - net (shipping)

225 (245) lb

 

102 (111) kg

13

Image 19
Contents 990-7080B 09/00 990-7080B 09/00 Electrical Safety Handling SafetyReplacement and Recycling of Batteries Page Table of Contents Page Unpacking ContentsHow to Unpack the SU 5000 UPS IntroductionPosition the UPS InstallationPlacement Installing the SU5000RMBInstall the Mounting Rails in the Rack Vac Units Connect Input Power to the UPSVac Units with Line Cord Vac Units for Hard Wire Connect Equipment to the UPS Install the BatteriesPower up the UPS and Accessories Install PowerChute and AccessoriesInitial Startup Operating Instructions SmartTrim Low BatteryLoad Bar Graph OverloadBattery Replacement Procedure Replacing the BatteryExtended storage User Configuration ItemsStorage Storage ConditionsOn-Battery Run Time Specifications Problem and Possible Cause Solution UPS will not turn on TroubleshootingLimited Warranty ServiceAPC Contact Information Vac Units 200/208 Vac UnitsRadio Frequency Interference Appendix B Transporting Your Smart-UPS